AOV Installation, Commissioning & Operating Manual
Approved Document Ref: UI-AOV-01 Issue 7.0
32
OPERATING
Disable Mode is used to disable or isolate individual circuits.
To initialise Disable Mode, firstly activate the controls by turning
the key switch or by entering the four digit code. Then press and
hold the Disable Mode button (1) for 3 seconds.
After 3 seconds the panel will bleep and the General Disablement
LED and Input LED will pulse slowly, indicating that the Input
circuit is in disable selection mode.
Pressing the Disable Mode button again will move disable selection mode to the Detector circuit and the
Detector LED will be pulsing instead. Subsequent presses will move the selection to PIR & Rain.
After the Rain circuit, pressing the button once more will move the selection back to the Input circuit again.
When the desired circuit or output to be disabled is indicated by a slow pulsing LED, use the ENTER
button to select it. Once selected the indicator LED will change to a rapid pulse. Pressing ENTER again will
toggle the circuit between disabled and enabled. Then use the Disable
Mode button again to move to the next circuit. Any or all circuits can be
disabled simultaneously.
When all disablements have been set, press and hold the Disable Mode
button for 3 seconds again. This will exit the disable selection mode and
the panel will return to standby. All disabled circuits and the General
Disablement will now be indicated by a steady LED.
To enable the circuits again, repeat the above process using the Disable Mode button to select the circuit
and the ENTER button to remove the disablement.
Tip:
With the controls active, pressing the Disable Mode button briefly will reveal which circuits are disabled (as
opposed to in test mode). This is useful if using Disable Mode and Test Mode at the same time.
Test Mode is used when testing the vent control system. In test mode the devices in all circuits in test,
detectors and call points etc, can be activated and the panel will automatically reset, enabling the system
to be tested by one person. It is possible to test head removal monitoring rain sensors & PIR.
To initialise Test Mode, firstly activate the controls by turning the key
switch or by entering the four digit code. Then press and hold the Test
Mode button (2) for 3 seconds.
After 3 seconds the panel will bleep and the Test Mode LED will
illuminate
Pressing and holding the Test Mode button again for 3 seconds will
cancel the Test Mode.
DISABLE MODE
TEST MODE
OPEN
VENT
CLOSE
VENT
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
OPEN
VENT
CLOSE
VENT
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
OPEN
VENT
CLOSE
VENT
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Содержание AOV Series
Страница 36: ...www haes systems com ...