AOV Installation, Commissioning & Operating Manual
Approved Document Ref: UI-AOV-01 Issue 7.0
27
SETUP & PROGRAMMING
Use button 1 to scroll to the attribute that requires editing, inidicated by a pulsing LED as per table below.
Use button 2 to switch the attribute ON or OFF
Then use button 1 to move to the next attribute if required.
Press the ENTER button to return back to the circuit selection, indicated by a steady circuit LED.
( ) =
Default State
3121 Input Circuit Function Settings
Attributes
Input Circuit
Detector Circuit
Rain Circuit
PIR Circuit
LED Status
Fast
Pulse
Slow
Pulse
Fast
Pulse
Slow
Pulse
Fast
Pulse
Slow
Pulse
Fast
Pulse
Slow
Pulse
CIRCUIT LATCH
(Gen Alarm LED)
Latching
Non
Latching
Latching
Non
Latching
Latching
Non
Latching
Latching
Non
Latching
SHORT CIRCUIT
(Gen Fault LED)
Short cct
= alarm
Short cct
= fault
Short cct
= alarm
Short cct
= fault
Short cct
= alarm
Short cct
= fault
Short cct
= alarm
Short cct
= fault
DETECTOR REMOVAL
(Gen Disable LED)
Detector
Removal
On
Detector
Removal
Off
4
1
4
1
Thermostat Controlled Ventilation Mode
This option allows for thermostat control of vent opening by using a thermostat to switch in a 4K7
resistance between the VENT CONT OP and COM terminals. This will allow the vent to open a set
distance – either 10%, 20% or 50% of full opening – when the pre-set temperature on the thermostat is
reached.
Enter the above code and press ENTER button.
The Vent Open Red LED will be rapidly pulsing. Press ENTER button to set the required amount of Vent
opening as indicated by the Input and Detector Yellow Fault LED’s on the display as shown.
Both Input and Detector LED’s OFF = Default setting. This function is not selected i.e normal operation
of the VENT CONT switch.
Input LED ON = 10% of full opening.
Detector LED ON = 20% of full opening.
Both Input and Detector LED’s ON = 50% of full opening.
Successive pressing of ENTER button will cycle through the above settings until the returning to the
original state (both Input and Detector LED’s OFF = normal operation).
When the required Vent opening setting is indicted press button 1 and hold for appox. 3 second to return
to Main Display.
*
*
*
*
*
*
*
*
*
CIRCUIT TO BE EDITED
- LED status when
NOT
in Edit Mode
- Fast Pulse Status indicated by ‘STEADY’ LED
- Slow Pulse Status indicated by LED ‘OFF’