AOV Installation, Commissioning & Operating Manual
Approved Document Ref: UI-AOV-01 Issue 7.0
31
OPERATING
Keypad
OPEN
VENT
CLOSE
VENT
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
OPEN VENT (red):
Use to activate the vent outputs to the open position.
CLOSE VENT
(blue):
Use to activate the vent outputs to the closed position.
RESET (green):
Resets the panel back to standby mode.
1: (Disable Mode)
With controls active, use to disable circuits or vent outputs (see DISABLE MODE section). Also has the
numeric value 1 for code entry.
2: (Test Mode)
With controls active, use to put circuits into test mode (see TEST MODE section). Also has the numeric
value 2 for code entry.
3: (Mute Buzzer)
Mutes the panels internal alarm and fault buzzer. (The buzzer will still blip every 5-6 seconds during
an alarm or fault condition unless disabled in the programming functions). This function is operational
without the need to activate controls. Also has the numeric value 3 for code entry.
4: (Test Lamps &
Buzzer)
Use this button to illuminate all LEDs and sound the internal buzzer to check that they are working
correctly. This function is operational without the need to activate controls. Also has the numeric value
4 for code entry.
ENTER:
This button is used to confirm code entries.
LED On
LED Pulsing
Vent Open
Vent in open position
Vent opening
Vent Closed
Vent in closed position
Vent closing
Vent Open/ PIR
N/A
Vent closing stopped while PIR active. This
requires the RESET button to be pressed to
make the vent move again
Input
N/A
Input faulty or disabled
Detector
Detector circuit open circuit
Detector circuit faulty, disabled or detector
removed
Supply Healthy
Power on
N/A
General Alarm
N/A
Input or Detector input alarm is active
General Fault
N/A
Indicates one or more faults are present
General Disablement
Indicates circuits are disabled
Disablement selection mode is active
Test Mode
Panel test mode is active
N/A
Rain Status
Rain input is active
Rain input is faulty or disabled
PIR Status
PIR input is active
PIR input is faulty or disabled
Power Supply Fault
N/A
Mains failure or battery fault
System Fault
Panel not functional
Panel has recovered from a system fault
Access Level
Indicates controls are activated (access level
2)
Indicates panel is in engineering mode
(access level 3)
Status LED Indicators
Some buttons and indicators have other functions within the engineering facilities. These functions are
described in the relevant sections.