AOV Installation, Commissioning & Operating Manual

Approved Document Ref: UI-AOV-01 Issue 7.0

20

INSTALLATION

Typical panel layout

Drawing shows typical internal layout of the AOV-3 panel cabinet with two 3.2Ah, 12v batteries fitted

MAINS CONNECTIONS

Do not connect the mains supply to the panel 
until you are fully conversant with the layout and 
features of the equipment.

A rating plate is attached to the power supply  
module describing the nature of the supply 
permitted.

The incoming mains supply should be brought 
into the panel via one of the knockouts provided.

A suitable cable gland must be used to secure 
the outer sheath of the cable used. The earth 

must  first  be  connected  to  the  primary  earth 

stud (peg) marked with a          symbol, using a 
suitable ring crimp.

Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the 

terminal block while leaving the earth connection intact.

The Loose Ferrite Inductor must be fitted as shown on the mains input to the power supply module for 
the panel to comply with EMC regulations. This applies to models; AOV-5, AOV-5H, AOV-10 & AOV-10H.

V+

V-

E

N

L

Fit inductor

during installation

Incoming mains wiring

+ -

12V

- -

PSU10A

+ +

+ -

+ -

+ -

+ - + - + - + -

C

NC

NO

C

NC

NO

IP

OP

OP

CL

COM

ON

OFF

COM

COM

ALARM

FAULT

AUX

ACT 1

+ -

ACT 2

INPUT

DETECTOR

RAIN

PIR

0/10V

BATTERY

VENT CONT

FIREMAN SW

1

2

3

4

5

6

7

ON

12V 3.2Ah VRLA BATTERY

12V 3.2Ah VRLA BATTERY

Содержание AOV Series

Страница 1: ...Installation Commissioning Operating Manual Automatically Opening Vent Control Panel Approved Document UI AOV 01 Issue 7 0 ...

Страница 2: ... the system as a whole The manufacturer s policy is one of continuous improvement and we reserve the right to make changes to product specifications at our discretion and without prior notice E O E IMPORTANT SAFETY NOTES Haes Systems Ltd Unit 3 Horton Industrial Park UB7 8JD 15 Model Number 3 Amp Automatically Opening Vent control panel AOV 3 standard spec AOV 3H high spec 5 Amp Automatically Open...

Страница 3: ... DESCRIPTION FUNCTIONS 12 DETECTOR CIRCUIT CONVENTIONAL WIRIING SCHEMATIC 16 DETECTOR CIRCUIT TWIN WIRE WIRIING SCHEMATIC 17 INSTALLATION 18 SAFETY 18 ESD PRECAUTIONS 19 GENERAL 19 MOUNTING THE CABINET 19 MAINS CONNECTIONS 20 CONNECTING THE BATTERIES 21 SETUP PROGRAMMING 22 TWIN WIRE MODE 22 DIL SWITCH OPTIONS 23 LEVEL 3 ENGINEERING OPTIONS 23 OPERATING 29 PANEL CONTROLS INDICATIONS 29 DISABLE MOD...

Страница 4: ...odes and features table All variations are supplied in a sheet steel enclosure suitable for wall mounting with a hinged lockable front access door The panels can be semi recessed using a suitable recessing bezel Cable entry is via 20mm knockouts located at the top and rear of the cabinet Different key types are used for the door lock and the activate controls key switch It is also possible to enab...

Страница 5: ...p 308W x 260H x 80D 3 2Ah A S E F M ACT x1 CA CF AOV 3H 3 Amp 308W x 260H x 80D 3 2Ah A S R P E F B M ACT x2 CA CF BMS AOV 5 5 Amp 460W x 310H x 110D 12Ah A S E F M ACT x1 CA CF AOV 5H 5 Amp 460W x 310H x 110D 12Ah A S R P E F B M ACT x2 CA CF BMS AOV 10 10 Amp 460W x 310H x 110D 12Ah A S E F M ACT x1 CA CF AOV 10H 10 Amp 460W x 310H x 110D 12Ah A S R P E F B M ACT x2 CA CF BMS Inputs Outputs A Al...

Страница 6: ...AOV Installation Commissioning Operating Manual Approved Document Ref UI AOV 01 Issue 7 0 4 ABOUT THIS PANEL Vent Control System 57mm 80mm 260mm 308mm 250mm 300mm AOV 3 CABINET ...

Страница 7: ...AOV Installation Commissioning Operating Manual Approved Document Ref UI AOV 01 Issue 7 0 5 ABOUT THIS PANEL AOV 5 10 CABINET 95mm 110mm 310mm 455mm 300mm 450mm Vent Control System ...

Страница 8: ...rols PCB 12V PSU10A C NC NO C NC NO IP OP OP CL COM ON OFF COM COM ALARM FAULT AUX ACT 1 ACT 2 INPUT DETECTOR RAIN PIR 0 10V BATTERY VENT CONT FIREMAN SW 1 2 3 4 5 6 7 ON 1 2 3 4 ENTER OPEN VENT CLOSE VENT RESET 1 2 3 4 ENTER OPEN VENT CLOSE VENT RESET TPCA016V H Master PCB TPCA02 AOV LED Display Controls PCB for AOV 3 control panels TPCA03 AOV LED Display Controls PCB for AOV 5 10 control panels ...

Страница 9: ...l safe Unfused max 3A 30v dc 0 10v control input output 100mA 12v dc supply output for PIR Magnetic vent output maintained Max 1A 28v dc Conventional Twin Wire smoke detector input Actuator motor drive outputs fused 10A subject to PSU ratings 4K7 Ω 470 Ω Trigger alarm input 4K7 Ω 470 Ω Rain sensor input PIR sensor input Vent control switch inputs Firemans switch inputs 12V PSU10A C NC NO C NC NO I...

Страница 10: ...dc Unfused Aux Maintained magnetic vent output 28v dc Max 1 amp Fused 1 amp 20mm glass quick blow fuse ACT1 Dual polarity reversal actuator drive outputs 28v dc Max 8 amps Fused 10 amp 20mm glass quick blow fuse Input Alarm activating input 470R alarm 4K7 Ohm 5 0 25W EOL resistor Monitoring current limit 14mA unfused Detector Fire alarm zone circuit Conventionally wired detection circuit or Twin W...

Страница 11: ... F3 15A 250V Not accessible Power supply rating 5 Amp incl battery charge Max shared load 5A Power supply output voltage 25 7 29 7 vdc Set for batt charge O P 27 3v Maximum ripple 150mV p p Min max battery size and type 3 2Ah 12Ahr x 2 12volt VRLA Yuasa NP range Battery charging voltage 27 3 nom dc Battery charging output current 630mA Current limited 10 Ohms Max current drawn from batteries 10 Am...

Страница 12: ... Operating Manual Approved Document Ref UI AOV 01 Issue 7 0 10 ABOUT THIS PANEL V V E N L 24v ve output O P Voltage adjust default setting 27 3v at 20 o C 24v ve output Earth Neutral Live Mains input AOV 3 3 AMP POWER SUPPLY MODULE ...

Страница 13: ...ating Manual Approved Document Ref UI AOV 01 Issue 7 0 11 ABOUT THIS PANEL AOV 5 10 5 10 AMP POWER SUPPLY MODULE V V N L Live Neutral Earth Mains Input To ve on TPCA016 To ve on TPCA016 Output Voltage Adjust default setting 27 3v 20 o C ...

Страница 14: ...v output Switches off to release magnet in the alarm condition The output can be inverted using DIL switch 2 on the main PCB The 0 10v BMS input does not affect the operation of this output ACT1 ACT2 Fused motor drive outputs not normally powered Operated for a configurable time period of 10 to 120 seconds The default setting is 30 seconds this should be set to the time period required to open clo...

Страница 15: ...onal The circuit can be used in Twin Wire mode by selection of DIL switch 4 on the main PCB This allows use of 24v alarm sounders in reverse polarity on this circuit Note In this mode the detectors require special Sav Wire bases An alarm on the detector circuit will activate the vent outputs in the same way as the activation input Some programming options are available for this circuit please refe...

Страница 16: ...rol signals IP Accepts 0 10 volt dc signal in 1 volt steps per 10 Vent position is determined by running time which by default is 30 seconds i e 10 3 seconds running time 50 15 seconds etc COM This is 0 volts common reference for 0 10V input output OP This output represents the position of the vent according to the time run Provides feed back of the 0 10V input status and vent positional informati...

Страница 17: ...res should be terminated in the cabinet using the earthing terminal provided The maximum recommended cable length for a zone or sounder circuit is 1Km This however is highly dependant on the number and type of devices connected If in doubt cable load and resistance calculations should be undetaken to ensure devices are working within specified limits The mains supply to the control panel should be...

Страница 18: ...L FUNCTIONS DETECTOR CIRCUIT CONVENTIONAL SYSTEM SCHEMATIC REMOTE INDICATOR RIL58 _ 4K7 OHM END OF LINE RESISTOR DETECTOR R L1 L1 L2 IN OUT R L1 L1 L2 IN OUT R L1 L1 L2 IN OUT APOLLO S65 BASE 45681 201 APOLLO S65 BASE 45681 201 APOLLO S65 BASE 45681 201 MANUAL CALL POINT MCP1A R 470 1 2 3 4 _ _ 470 ...

Страница 19: ...ircuit the sounders are connected in reverse polarity to the detectors and call points Note Detector circuit configuration is set to Conventional by default Twin Wire mode must be set using DIL switch 4 on main PCB DETECTOR APOLLO TWIN WIRE BASE 45681 206 APOLLO TWIN WIRE BASE 45681 206 TWIN WIRE CALL POINT MCP1B R TW TWIN WIRE CALL POINT MCP1B R TW 1 2 3 4 _ _ 470 1 2 3 4 _ _ 470 VE VE MOTORISED ...

Страница 20: ... to anyone concerned with its use This equipment is designed to be operated from 230V AC 50 60 Hz mains supplies and is of Class I construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe ...

Страница 21: ... avoid damage to the control equipment The site chosen for the location of the panel should be clean dry and not subject to shock or vibration Damp salt air or environments where water ingress or extremes of temperature may affect the panel must be avoided The temperature should be in the range 5 to 40 C and the relative humidity should not exceed 95 Before mounting the cabinet remove the main PCB...

Страница 22: ...sed to secure the outer sheath of the cable used The earth must first be connected to the primary earth stud peg marked with a symbol using a suitable ring crimp Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block while leaving the earth connection intact The Loose Ferrite Inductor must be fitted as shown on the mains input t...

Страница 23: ...polling This is normal If the fault doesn t clear after 1 minute check connections The battery charging voltage is factory calibrated to 27 3vdc 0 2v 20o C This should not normally require adjustment Where battery problems are experienced the following information should be considered a If a battery is disconnected from the charger no voltage will appear on the output leads or terminals due to int...

Страница 24: ...rity to the detectors and call points i e detector circuit positive wire connects to detector base and call point positive terminals but sounder and beacon negative terminals 12V IP OP CL ON OFF COM COM ACT 2 TRIGGER SMOKE RAIN PIR 0 10V VENT CONT FIREMAN SW 1 2 3 4 5 6 7 ON 1 2 3 4 5 6 7 ON 1 2 3 4 5 6 7 ON To set the DETECTOR output to Twin Wire mode move switch 4 on the 7 way DIL switch located...

Страница 25: ... the Alarm Relay will operate when the Open Vent button is pressed Note The Alarm Relay will always operate for the Alarm Input and Detector Circuit alarm Switch 2 AUX INVERT If set to OFF down the magnetic vent output AUX is normally powered on maintained The voltage clears during an alarm condition or Vent Open status and is re instated following a reset or in Vent Closed status If set to ON up ...

Страница 26: ...se to indicate EDIT mode OPTION 1 Vent Open LED Change Remove Keypad Access Code The keypad can be used to activate the panel controls instead of using the key switch The default code is 1 2 3 4 however this can be changed It is also possible to disable the use of a code entry to enable controls forcing the use of the key switch only With the Vent Open LED pulsing The General Fault 1 General Disab...

Страница 27: ...ase or decrease the time by 10 seconds at a time if PIR status LED is OFF or 20 seconds at a time if PIR Status LED is ON Use button 4 to set PIR status LED On or OFF Maximum run time of 300 seconds can be set Press the ENTER button to set the time and return to the main menu Use this option to disable the battery monitoring i e batteries not installed With the Input LED pulsing the current status...

Страница 28: ...turned off For use with detectors which are not compatible with this function Enter the above code and press the ENTER button The Input LED will light This indicates setting the above attributes for the activate Input circuit The General Alarm General Fault General Disablement LEDs will show the current attribute settings for that circuit see table over page Use button 1 to move to the circuit tha...

Страница 29: ...led Ventilation Mode This option allows for thermostat control of vent opening by using a thermostat to switch in a 4K7 resistance between the VENT CONT OP and COM terminals This will allow the vent to open a set distance either 10 20 or 50 of full opening when the pre set temperature on the thermostat is reached Enter the above code and press ENTER button The Vent Open Red LED will be rapidly pul...

Страница 30: ...ts should be used to provide an instant un delayed alarm A 470Ω call point will be included in the dependency delay sequence By default this is set to off To set Detector circuit to Type A dependency mode enter the above code and press the ENTER button The Vent Open LED will pulse rapidly to indicate the detector circuit is under selection The Input LED indicates the status as per below press the ...

Страница 31: ... Indicator LEDs 8 Button Keypad For Controls And Programming Status Indicator LEDs Activate Controls Key Switch 8 Button Keypad For Controls And Programming Status Indicator LEDs Activate Controls Key Switch RESOUND SILENCE RESET ENTER 1 2 3 4 General Disablement Test Mode Rain Status PIR Status Power SupplyFault System Fault Access Level On Off Supply Healthy General Alarm General Fault Activate ...

Страница 32: ...emain active NOTE It is not possible to remove the key in the On position To activate the controls using the keypad enter the four digit code using buttons 1 4 The factory default code is 1 2 3 4 but can be changed in the engineering functions After entering the four digit code press the ENTER button The Access Level indicator LED will light and all buttons on the keypad will now be operational Af...

Страница 33: ...ional without the need to activate controls Also has the numeric value 4 for code entry ENTER This button is used to confirm code entries LED On LED Pulsing Vent Open Vent in open position Vent opening Vent Closed Vent in closed position Vent closing Vent Open Closed PIR N A Vent closing stopped while PIR active This requires the RESET button to be pressed to make the vent move again Input N A Inp...

Страница 34: ...or 3 seconds again This will exit the disable selection mode and the panel will return to standby All disabled circuits and the General Disablement will now be indicated by a steady LED To enable the circuits again repeat the above process using the Disable Mode button to select the circuit and the ENTER button to remove the disablement Tip With the controls active pressing the Disable Mode button...

Страница 35: ...ton fig 1 regardless of alarm condition this should only be done if no smoke is present 6 When fully satisfied that there is no alarm conditions present return to the control panel and Activate Controls then press the green Reset button see fig 2 The panel should return to normal with the green SUPPLY HEALTHY LED and the amber ACCESS LEVEL LED illuminated on the display Turning off Activate Contro...

Страница 36: ...www haes systems com ...

Отзывы: