11-4
Figure11-5 Routing MPU cables
Routing fabric module cables
As a best practice, route the fabric module cables along the nearest cable management fingers and
cable management brackets.
For example, the router is installed with CR-19K-MSFU-20C fabric modules. As shown in
each CR-19K-MSFU-20C fabric module has 6 groups of ports, with 3 groups on the upper half of the
module and 3 groups on the lower half. Use the cable management fingers and cable management
brackets for the cables as follows:
•
Cables from the ports on the upper half of each module
—Upper cable management finger
for the slot.
•
Cables from the ports on the lower half of each module
—Lower cable management finger
for the slot.
•
Cables from the fabric modules in slots 22 to 24 (left slots)
—Left cable management
bracket.