P/N G610B 
April, 2016 (Rev 0)

 

 

Page 2

 

 

 

 

 

 
INTRODUCTION 

 

There exist a variety of causes for cooking fires, but 
most  causes  involve  unattended  cooking.  Here  are 
some  tips  to  help  prevent  a  cooking  fire  in  your 
kitchen. 

 

FIRE PREVENTION TIPS:  

 

 

Never leave the kitchen when cooking food.  

 

Use  fresh  cooking  oil  whenever  possible.  The 
ignition  temperature  of  used  cooking  oil  can  be 
lower  than  normal  and  it  may  contain  left-over 
solids which can ignite. 

 

Smoke generated from cooking oil is an indication 
that  the  temperature  of  the  oil  has  exceeded  the 
desired cooking temperature of 350-375 F.  As the 
oil  temperature  increases,  the  smoke  produced 
will  increase  significantly.    If  this  occurs,  simply 
turn the burner down or turn it off to prevent the oil 
from reaching its ignition temperature.  

 

Be  sure  to  keep  the  cooking  surface  and 
surrounding  counter  areas  clean  and  clear  of 
combustible materials which could ignite. 

 

If  you  must  leave  the  kitchen  when  frying  food, 
turn  the  burner  off  or  remove  the  pan  from  the 
burner until you return. 

 

IN CASE OF A FIRE:  

 

NEVER

  attempt  to  move  a  burning  cooking  vessel 

after  it  has  ignited.  Any  movement  could  splash 
burning  grease  and  spread  the  fire  or  cause  severe 
injury.

 

NEVER  TRY  TO  EXTINGUISH  A  GREASE 

FIRE USING WATER

. Evacuate the kitchen and call 

the  Fire  Department  immediately,  then  alert  others 
and evacuate the building. Let your Guardian G600-B 
extinguish any range top fire. Because of the heat and 
smoke  associated  with  a  cooking  fire,  it  is 
recommended  that  you  wait  at  least  30  minutes  after 
the  fire  has  been  extinguished  before  re-entering  the 
building and approaching your kitchen range.

  

 

OPERATION:

   

 

The  Guardian  G600-B  system  is  an  automatic  fire 
suppression system designed to detect and extinguish 
cooking  fires  on  residential  type  range  tops.  In  the 
event of a stovetop fire, the sensors will activate at a 
pre-set  temperature  and  signal  the  main  CPU  board. 
The main CPU automatically sends a signal to release 
the  extinguisher  valve  assembly,  releasing  the 
extinguishing  agent  and  simultaneously  activates  the 
CPU-mounted  alarm,  and  the  fuel  shutoff  which 
disconnects the gas and/or electricity to the range.

 

 

 
 
 
 
 

 
APPLICATION AND LIMITATION  

 

 

The  Guardian  G600-B  is  designed  and  Listed  for  the 
protection  of  30  in.  wide,  gas  or  electric  residential 
range tops when installed in conjunction with a 30 inch 
wide  exhaust  hood  or  microwave/exhaust  hood 
combination  with  a  flat  ferromagnetic  underside.  The 
extinguishing system is intended for installation within a 
kitchen cabinet having an internal height of 12" or taller 
and  located  either  directly  above,  or  adjacent  to  the 
range top and exhaust hood. 

 

 

Guardian  G600-B  System  is  acceptable  for  use  with 
either a ductless or ducted exhaust hood. 

 

 

The  extinguisher  enclosure  assembly  is  intended  for 
installation within a protected space, such as a kitchen 
cabinet as outlined in this manual.  

 

 

Only  components  identified  by  part  numbers  in  this 
manual are authorized for use with the Guardian G600-
B system unless expressly stated in this manual. 

 

 

All electrical wiring and  alarm connections are to be in 
compliance  with  the  National  Electrical  Code  (NFPA 
70),  National  Fire  Alarm  Code  (NFPA  72)  and  any 
applicable state or local municipal codes.  

 

RESIDENTIAL RANGE-TOP USE ONLY  

 

 

The Guardian G600-B extinguishing system is designed 
and  thoroughly  tested  in  accordance  with  UL  Subject 
300A  for  normal  residential  type  cooking  applications 
which  originate  from  residential  range  top  cooking 
appliances  when  used  in  conjunction  with  a  flat  faced 
(bottom) exhaust hood or microwave hood only. 

 

 

The  Guardian  G600-B  extinguishing  system  is  not 
intended  for  the  protection  of  commercial  "restaurant-
style" cooking equipment.  

 

 

The  maximum  range  top  cooking  surface  protected  by 
the  Guardian  G600-B  System  is  720

 

square  inches 

measuring 30" wide and 24" deep. 

 

 

The  Guardian  G600-B  is  not  designed  or  intended  for 
the  protection  of  areas  adjacent  to,  or  within  the 
residential  range  top,  such  as  nearby  counter  tops  or 
within the range oven.

 

 

PACKING LIST  

 

Check  contents  for  missing

 

or  damaged

 

parts 

(

see 

FIGURES  1,  2,  3  &  4).  Check  fire  extinguisher  for  proper 
operating  pressure.  Needle  should  point  in  the  operable 
(green)  zone.  Report  any  damage  or  missing  parts  to  the 
manufacturer before starting installation.  

 

CAUTION:  
DO NOT REMOVE SAFETY PIN FROM FIRE  
EXTINGUISHER AT THIS TIME!!!

 

 

 

NOTE:  

 

Additional equipment or components necessary to install the system in accordance with the instructions and limitations listed 
are to be provided by the authorized installer if not purchased with the basic system (i.e., electrical Wire, wire mold, shut-off 
components,  etc.).  Additional  equipment  and  components  may  be  obtained  from  a  Guardian  Safety  Solutions  International 
distributor or the manufacturer

.

 

Permit Number:

20-04649

Содержание G600-B

Страница 1: ...OPERATION INSPECTION AND MAINTENANCE MANUAL MODEL G600 B RESIDENTIAL RANGE TOP EXTINGUISHER UNIT UL FILE NO EX 3940 P N G610B APRIL 2016 REV 0 8701 John Carpenter Freeway Suite 230 Dallas TX 75247 Per...

Страница 2: ...11B 4 Prong Shutoff FIGURE 11C Hardwire Shutoff FIGURE 12 Electric Shutoff Connector Configuration FIGURE 13 Electric Shutoff Interconnect Identification FIGURE 14 Electric Shutoff Installation FIGUR...

Страница 3: ...al range tops when installed in conjunction with a 30 inch wide exhaust hood or microwave exhaust hood combination with a flat ferromagnetic underside The extinguishing system is intended for installa...

Страница 4: ...ectrical or gas stoves ready for installation in the kitchen cabinet and range hood over the stove Sensor Assembly P N G605 A Distribution Assembly P N 604 A Enclosure Extinguisher Assembly P N G699 B...

Страница 5: ...GUARDIAN G600 B AS A HAND HELD PORTABLE EXTINGUISHER SERIOUS INJURY COULD RESULT FROM MISUSE THE CHEMICAL AGENT USED IN THE GUARDIAN G600 B IS NOT REGARDED AS A TOXIC MATERIAL BUT CAN CAUSE IRRITATIO...

Страница 6: ...owly flashing red indicator If the main unit passes all 6 tests upon reset the result is a display of the green indictor for 2 seconds whereupon it enters Fire Detect Mode and the system is armed 2 Di...

Страница 7: ...if the diagnostic failure is a low battery Approximately once per minute the battery is checked If it is low there will be a short chirp to indicate that the battery needs to be replaced The unit will...

Страница 8: ...nd for easy connection to the valve head of the extinguisher Inside the housing there are 2 nozzles mounted in fittings connected by a stainless steel tube The assembly is installed underneath the hoo...

Страница 9: ...xtinguisher Assembly Before Drilling measure the route and make certain that the sensor cable and stainless steel braided hose are long enough to connect to the Guardian G600 B System Enclosure Exting...

Страница 10: ...crews to anchor into the hood above and two 1 1 4 screws to secure to the wall behind Screws in the wall must be located where they will go into the walls studs or into a wall anchor Screws going into...

Страница 11: ...ng Gauge provided adjust the nozzles to the correct angle based on the height determined in step 14 This is done by placing the Gauge in the housing and aligning the nozzles spray hole with the corres...

Страница 12: ...he electric shutoff is activated or an interruption in power occurs it must be reset See Reset Stove p 12 INSTALLATION NOTE Ensure the Electric Shutoff is installed within the same room as the Main CP...

Страница 13: ...and 25 Reset Stove 1 The electric stove shutoff unit may be reset by locating the circuit breaker supplying power to the stove and turning it off and then back on or 2 Momentarily unplugging the shuto...

Страница 14: ...6 1 on the incoming service line to the stove Adhere to manufacturers installation and maintenance instructions Wiring must comply with local and national electrical codes The solenoid valve is design...

Страница 15: ...s compatible with both the interconnect cable and the Wireless Tx Rx Either interconnect option is available and can plug into the gas shutoff In some cases a wireless version of the shutoff device ma...

Страница 16: ...ic Failure Code occurs 1 Verify that the fuel shut off is powered and is reset See page 12 for Electric page 14 for Gas 2 Next check that the solenoid release latch is engaged See Figure 28 p 19 and t...

Страница 17: ...on of the Main CPU board includes a Motor Test Advance Button and includes a TRIP MOTOR connection on the board instead of a VALVE connection See Figure 26 Note Test the Trip Motor and Cam Monthly by...

Страница 18: ...he range top burners and activate the alarm or other electrical accessory Once activated the automatic sequence cannot be interrupted The manual pull station is installed at a height not exceeding 60...

Страница 19: ...vide an interface for a 120 volt 5A alarm strobe This assembly has a Plug Play configuration for ease of installation Install in optimum location for visibility This feature is mainly used with the st...

Страница 20: ...ng fire extinguisher unit appliance nozzles sensor distribution assembly and shutoffs Replace battery in the central processing unit control board annually from the date of installation Use only Durac...

Страница 21: ...gent cylinder has been completely expelled and the pull pin is re installed in the handle prior to disconnecting the quick connect 4 Disconnect the quick connect below the handle and remove the distri...

Страница 22: ...1 18 24 25 G615 A Wireless Tx and Rx and AC DC 18 24 G702 Wireless Receiver Rx Assembly 18 25 G701 Wireless Transmitter Tx Assembly 14 17 G316 A Gas Shutoff Assembly 1 14 17 G316 1 Gas Valve 1 14 17 G...

Страница 23: ...and that the connectors are fully mated Press the reset button on the Main CPU and verify the green indicator momentarily lights up Verify power is getting to stove by testing a burner If there is no...

Страница 24: ...f any unknown wireless interference occurs from a site condition the Interconnect Cable may have to be used Gas Shutoff P N G316 A Problem No Electrical Power To Stove Confirm that power is supplied a...

Страница 25: ...switch to open the gas valve to the stove The gas flow indicator light will illuminate Verify that the Interconnect cable between the Main CPU control board and the Gas Shutoff Control box is plugged...

Страница 26: ...perform Arming the System on page 15 again If power gas to the stove stays on after a diagnostic test and there are no Diagnostic Code beeps then replace the Main CPU board If the stove successfully...

Страница 27: ...TRAC 1 800 535 5053 Account Number 78764 SECTION II Hazard Identification GHS Classification Acute Toxicity Category 5 Eye Irritation Category 2B Skin Irritation Category 3 GHS Label Elements Hazard S...

Страница 28: ...on is an extinguishing media There are NO extinguishing media which must not be used for safety reasons NO special protective equipment is needed for fire fighters Wear protective equipment appropriat...

Страница 29: ...o C About 230 o F Flash point None to boiling Flammability solid gas Not flammable Explosive properties Not explosive Oxidizing properties Not an oxidizer Vapor Pressure About 12mm Hg Relative Densit...

Страница 30: ...harm to the environment is expected from this preparation Please Note Although this material is not considered hazardous when contained in a stored pressure fire extinguisher pressurized with a nonfl...

Страница 31: ...l advice S 36 Wear suitable protective clothing THE ABOVE INFORMATION IS BELIEVED TO BE CORRECT BUT DOES NOT PURPORT TO BE ALL INCLUSIVE AND SHALL BE USED ONLY AS A GUIDE GUARDIAN SAFETY SOLUTIONS INT...

Страница 32: ...8701 John Carpenter Freeway Suite 230 Dallas TX 75247 Toll Free 800 786 2178 Fax 972 594 7826 www guardianssi com Permit Number 20 04649...

Отзывы:

Похожие инструкции для G600-B