P/N G610B
April, 2016 (Rev 0)
Page 25
TROUBLESHOOTING GUIDE
(continued)
CAUTION:
DURING TROUBLESHOOTING
PROCEDURES MAKE SURE A SPARE
SAFETY PULL PIN IS INSTALLED IN THE
EXTINGUISHER HANDLE. THE SPARE
SAFETY PULL PIN MUST BE REMOVED
FROM THE HANDLE WHEN
TROUBLESHOOTING IS COMPLETE.
•
If activation occurs, reset the shutoff, temporarily
connect an interconnect cable instead of the
Wireless Tx/Rx and perform “Arming the System”
on page 15 again.
If power/gas to the stove stays
on after a diagnostic test, and there are no
Diagnostic Code “beeps” then replace the Main
CPU board.
•
If the stove successfully shut-off using the
interconnect cable then try installing the Wireless
Transmitter/Receiver again, reset the gas shut-off
and perform “Arming the System” procedures on
Page 15. If the stove still does not shutoff, then
replace the Wireless Transmitter/Receiver.
•
If any unknown wireless interference occurs from
a site condition the Interconnect Cable may have
to be used.
Permit Number:
20-04649