Cylinder Pressure/Temperature Graph

 
 
 
 
 
 
 
 
 

INSPECTION AND MAINTENANCE

 

Monthly

,  Check  the  discharge  nozzles  and  heat  detection 

sensors  for  visual  signs  of  obstruction  and  check  the 
pressure  gauge.  If  the  needle  points  to  the  "recharge"  or 
"overcharged"  zone,  contact  an  authorized  Guardian  Safety 
Solutions  representative  immediately  for  service.  For  G600-
C  Motor/Cam  System  see  Page  16  for  additional 
instructions. 

 

Annually

,  a  Guardian  Safety  Solutions,  Intl.  Distributor, 

holding all appropriate licenses/approvals for the jurisdiction 
in which the system is installed, shall test the function of and 
inspect  all  components,  including  fire  extinguisher  unit, 
appliance  nozzles,  sensor,  distribution  assembly  and 
shutoffs.  Replace  battery  in  the  central  processing  unit 

control board annually from the date of installation. Use only 
Duracell  MN1604  or  Energizer  EN22.  Keep  the  Guardian 
G600-B system free of cooking grease residue.  

 

Every 

Twelve (12)  years,

 a Guardian Safety Solutions, Intl. 

Distributor, holding all appropriate licenses/approvals for the 
jurisdiction in which the system is installed, shall empty and 
hydrostatically test the fire extinguisher cylinder and flexible 
discharge  hose  assembly  to  the  appropriate  test  pressure 
(300psi).  Refill  extinguisher  using  new  wet  chemical  agent 
by  purchasing  a  recharge  kit  (P/N  G-BRK)  from  Guardian 
Safety Solution’s, Intl. (See NFPA 17A, Par. 7.5.3).  

DO NOT

 combine chemicals.

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Solenoid Position 

ENGAGED 

FIGURE 28 

DISENGAGED 

PRESSURE(PSI) 

Based upon Ideal Gas Law 

FIGURE 29 

Permit Number:

20-04649

Содержание G600-B

Страница 1: ...OPERATION INSPECTION AND MAINTENANCE MANUAL MODEL G600 B RESIDENTIAL RANGE TOP EXTINGUISHER UNIT UL FILE NO EX 3940 P N G610B APRIL 2016 REV 0 8701 John Carpenter Freeway Suite 230 Dallas TX 75247 Per...

Страница 2: ...11B 4 Prong Shutoff FIGURE 11C Hardwire Shutoff FIGURE 12 Electric Shutoff Connector Configuration FIGURE 13 Electric Shutoff Interconnect Identification FIGURE 14 Electric Shutoff Installation FIGUR...

Страница 3: ...al range tops when installed in conjunction with a 30 inch wide exhaust hood or microwave exhaust hood combination with a flat ferromagnetic underside The extinguishing system is intended for installa...

Страница 4: ...ectrical or gas stoves ready for installation in the kitchen cabinet and range hood over the stove Sensor Assembly P N G605 A Distribution Assembly P N 604 A Enclosure Extinguisher Assembly P N G699 B...

Страница 5: ...GUARDIAN G600 B AS A HAND HELD PORTABLE EXTINGUISHER SERIOUS INJURY COULD RESULT FROM MISUSE THE CHEMICAL AGENT USED IN THE GUARDIAN G600 B IS NOT REGARDED AS A TOXIC MATERIAL BUT CAN CAUSE IRRITATIO...

Страница 6: ...owly flashing red indicator If the main unit passes all 6 tests upon reset the result is a display of the green indictor for 2 seconds whereupon it enters Fire Detect Mode and the system is armed 2 Di...

Страница 7: ...if the diagnostic failure is a low battery Approximately once per minute the battery is checked If it is low there will be a short chirp to indicate that the battery needs to be replaced The unit will...

Страница 8: ...nd for easy connection to the valve head of the extinguisher Inside the housing there are 2 nozzles mounted in fittings connected by a stainless steel tube The assembly is installed underneath the hoo...

Страница 9: ...xtinguisher Assembly Before Drilling measure the route and make certain that the sensor cable and stainless steel braided hose are long enough to connect to the Guardian G600 B System Enclosure Exting...

Страница 10: ...crews to anchor into the hood above and two 1 1 4 screws to secure to the wall behind Screws in the wall must be located where they will go into the walls studs or into a wall anchor Screws going into...

Страница 11: ...ng Gauge provided adjust the nozzles to the correct angle based on the height determined in step 14 This is done by placing the Gauge in the housing and aligning the nozzles spray hole with the corres...

Страница 12: ...he electric shutoff is activated or an interruption in power occurs it must be reset See Reset Stove p 12 INSTALLATION NOTE Ensure the Electric Shutoff is installed within the same room as the Main CP...

Страница 13: ...and 25 Reset Stove 1 The electric stove shutoff unit may be reset by locating the circuit breaker supplying power to the stove and turning it off and then back on or 2 Momentarily unplugging the shuto...

Страница 14: ...6 1 on the incoming service line to the stove Adhere to manufacturers installation and maintenance instructions Wiring must comply with local and national electrical codes The solenoid valve is design...

Страница 15: ...s compatible with both the interconnect cable and the Wireless Tx Rx Either interconnect option is available and can plug into the gas shutoff In some cases a wireless version of the shutoff device ma...

Страница 16: ...ic Failure Code occurs 1 Verify that the fuel shut off is powered and is reset See page 12 for Electric page 14 for Gas 2 Next check that the solenoid release latch is engaged See Figure 28 p 19 and t...

Страница 17: ...on of the Main CPU board includes a Motor Test Advance Button and includes a TRIP MOTOR connection on the board instead of a VALVE connection See Figure 26 Note Test the Trip Motor and Cam Monthly by...

Страница 18: ...he range top burners and activate the alarm or other electrical accessory Once activated the automatic sequence cannot be interrupted The manual pull station is installed at a height not exceeding 60...

Страница 19: ...vide an interface for a 120 volt 5A alarm strobe This assembly has a Plug Play configuration for ease of installation Install in optimum location for visibility This feature is mainly used with the st...

Страница 20: ...ng fire extinguisher unit appliance nozzles sensor distribution assembly and shutoffs Replace battery in the central processing unit control board annually from the date of installation Use only Durac...

Страница 21: ...gent cylinder has been completely expelled and the pull pin is re installed in the handle prior to disconnecting the quick connect 4 Disconnect the quick connect below the handle and remove the distri...

Страница 22: ...1 18 24 25 G615 A Wireless Tx and Rx and AC DC 18 24 G702 Wireless Receiver Rx Assembly 18 25 G701 Wireless Transmitter Tx Assembly 14 17 G316 A Gas Shutoff Assembly 1 14 17 G316 1 Gas Valve 1 14 17 G...

Страница 23: ...and that the connectors are fully mated Press the reset button on the Main CPU and verify the green indicator momentarily lights up Verify power is getting to stove by testing a burner If there is no...

Страница 24: ...f any unknown wireless interference occurs from a site condition the Interconnect Cable may have to be used Gas Shutoff P N G316 A Problem No Electrical Power To Stove Confirm that power is supplied a...

Страница 25: ...switch to open the gas valve to the stove The gas flow indicator light will illuminate Verify that the Interconnect cable between the Main CPU control board and the Gas Shutoff Control box is plugged...

Страница 26: ...perform Arming the System on page 15 again If power gas to the stove stays on after a diagnostic test and there are no Diagnostic Code beeps then replace the Main CPU board If the stove successfully...

Страница 27: ...TRAC 1 800 535 5053 Account Number 78764 SECTION II Hazard Identification GHS Classification Acute Toxicity Category 5 Eye Irritation Category 2B Skin Irritation Category 3 GHS Label Elements Hazard S...

Страница 28: ...on is an extinguishing media There are NO extinguishing media which must not be used for safety reasons NO special protective equipment is needed for fire fighters Wear protective equipment appropriat...

Страница 29: ...o C About 230 o F Flash point None to boiling Flammability solid gas Not flammable Explosive properties Not explosive Oxidizing properties Not an oxidizer Vapor Pressure About 12mm Hg Relative Densit...

Страница 30: ...harm to the environment is expected from this preparation Please Note Although this material is not considered hazardous when contained in a stored pressure fire extinguisher pressurized with a nonfl...

Страница 31: ...l advice S 36 Wear suitable protective clothing THE ABOVE INFORMATION IS BELIEVED TO BE CORRECT BUT DOES NOT PURPORT TO BE ALL INCLUSIVE AND SHALL BE USED ONLY AS A GUIDE GUARDIAN SAFETY SOLUTIONS INT...

Страница 32: ...8701 John Carpenter Freeway Suite 230 Dallas TX 75247 Toll Free 800 786 2178 Fax 972 594 7826 www guardianssi com Permit Number 20 04649...

Отзывы:

Похожие инструкции для G600-B