FST 75/150
260-2210-002 EN064
Page 20 / 37
Extended functions
7.1
Interlock-system
Save
w
0
Interlock-system deactivated
Press rotary switch
1
Interlock-system activated
7.2*
Door open command transmission if interlock-system in ON
Save
w
0..10 Delay of opening Door 2 if Door 1 is closed in sec
Press rotary switch
*On command the choosen Door 1 is opened. After closing of Door 1 an open command for Door 2 is given.
7.7**
Delayed opening
Save
W
0
Delay deactivated
3..50 Time-setting 3-50 seconds. Starts after opening command
Press rotary switch
7.8**
Delayed closing
Save
W
0
Delay deactivated
3..50 Time-setting 3-50 seconds. Starts after closing command
Press rotary switch
** In combination with a relay i.e. for delayed opening, this function allows the operation of a all-round light
as opening warning.
In case of double-winged or overlapped doors an appropriate forerun may be activated.
8.5
Setting of service interval
Save
W
0
Function service interval disabled
1..99 Setting of cycles for service of the door.
Number of cycles = setting x 1000
Press rotary switch
8.6
Service interval reaction
Save
W
0
No reaction
1
Display: CS
Press rotary switch
2
Display: CS and degrade to deadman control
3
Display: CS and degrade to deadman control
Reset for 500 cycles by pressing Stop-Button for 3 seconds