Free configuration of Relays K3-K8
The output relays K3-K8 may be freely configured by some functions. For that choose the desired relay in
the main menu and choose the function in the sub menu. The sub menu is available for each relay.
To use the relays for traffic lights there are complete function sets to choose from. Please refer to chapter
„Configure traffic light functions for K5-K8“.
Relays K3 – K4:
2.7
Relay K3
save
W
0
No function
1
Impulse from intermediate stop position or programmed switch
point (see 51)
2
Permanent contact from intermediate stop position or
programmed switch point (see 51)
3
Traffic light function red
4
Traffic light function green
Press rotary switch
5
Position indicator “open”
6
Position indicator “close”
7
Flashing light function
8
Beacon
9
Fault alarm
•
F 1.3: Safety circuit DES
•
F 1.4: Emergency off contact actuated
•
F 2.5: Closed-safety edge 8k2 defective
•
F 2.7: Closed-pressure wave edge 1k2 defective
•
F 3.1: Upper area of emergency limit switch approached
•
F 3.2: Lower area of emergency limit switch approached
•
F 3.3: Limit switch
•
F 5.5: DES not active
•
F 5.6: Drive does not run
•
F 5.8: Speed exceeded
•
F5.9: Runtime error
•
F 6.5: Open-safety circuit 8k2 defective
•
F6.7: Open-safety circuit 1k2 defective
•
F 7.1: Stand still error
•
F 7.2: Wrong direction of rotation