FST 75/150
260-2210-002 EN064
Page 16 / 37
Adjust speeds
Important Information:
The necessary power of the inverter is dependant from wight, acceleration and speed of the site.
Modification of frequency through the menu directly changes the speed of the site. Increasing of frequency
leads to increasing of speed and therefor increasing of necessary power.
Dysfunction of operation possibly leads to an overload of the inverter. In that case the speed has to be
reduced to ensure a reliable operation.
4.1
Speed for opening
save
w=50
15..100 Opening with x Hz. Increasing of nominal frequency (Menu 05)
changes the adjustable range (max. 200 Hz).
Press rotary switch
4.2
Speed for closing
save
w=50
15..100 Closing with x Hz. Increasing of nominal frequency (Menu 05)
changes the adjustable range (max. 200 Hz).
Press rotary switch
4.3
Speed for swifter closing
(only in connection with DES)
save
w=0
15..100 Closing with x Hz. To disable function, set value to 0. The
changeover is enabled by programming the position (DES s.
Menu 44).
Press rotary switch
4.4
Switch point for lowering the closing speed
(only in connection with DES)
save
-.-
Use the internal keys to go to the required position
Stop key
4.5
Soft start opening
save
w=10
5..50
Duration of acceleration ramp in opening direction / 0.1 seconds
Press rotary switch
4.6
Soft coasting opening
save
w=10
5..50
Duration of deceleration ramp in opening direction / 0.1 seconds
Press rotary switch
4.7
Soft start closing
save
w=10
5..50
Duration of acceleration ramp in closing direction / 0.1 seconds
Press rotary switch
4.8
Soft coasting closing
save
w=10
5..50
Duration of deceleration ramp in closing direction / 0.1 seconds
Press rotary switch
4.9
Creep speed
save
w=10
5..50
Creep speed in Hz
Press rotary switch