INSTALLATION
19
ADICOS HOTSPOT-1000
410-2410-001 EN11
Wiring ADICOS-AAB
1
Open the cover on the ADICOS-ABB enclosure
2
Open the lower cable gland on the ADICOS-ABB
3
Thread the ADICOS connection cable through the lower cable gland and into the ADI-
COS-ABB
4
Connect the cable cores to the ADICOS-ABB connecting terminals as shown in the wiring
diagram
5
Close the cable gland on the ADICOS-ABB
6
Close the cover on the ADICOS-ABB enclosure
NOTE!
More information on how to install the ADICOS branching and connection box
can be found in the
GTE manual, no. 430-2410-001
!
5.3.4 Wiring Variations
The actual wiring of the detector to the
ADICOS
branching and connection box can vary
depending on the system configuration. The following wiring diagrams show the most common
system configurations and wiring variations.
ADICOS BMZ / M-BM and external NT
+24 V 0 V M-Bus
A
M-Bus
B
B1 A1 B2 A2 X6e X7e X6a X7a
red black yellow green white brown pink blue violet gray
blue/red gray/pink
0 V
+24 V
PE
PE
+24 V
0 V
X7 (Stoer)
X6aus (Al)
X6ein (Al)
LOOP B
LOOP A
M-Bus A
M-Bus B
+
24 V
0 V
X7 (Stoer)
X6aus (Al)
X6ein (Al)
LOOP B
LOOP A
M-Bus A
M-Bus B
ADICOS-AAB
ADICOS-connection cable for detector
to next
ADICOS-AAB
ADICOS Power supply unit
NT V40-A3
0 V
+40 V
ADICOS BMZ-30
M-Busmaster
+ (24 V)
− (24 V)
M-Bus
M-Bus