INSTALLATION
15
ADICOS HOTSPOT-1000
410-2410-001 EN11
5.3.1 Cable Assignment
Color
Signal
Potential-free contact
Red
Operating voltage
24 ... 40 V DC, non-polarized
Black
Yellow
Relay output X6 e
Alarm (NO)
1
White
Relay output X6 a
Alarm (NO)
1
Brown
Relay output X7 a
Failure (NC)
Green
Relay output X7 e
Failure (NC)
Pink
Fire panel interface B – in
Auxiliary assembly
(option-
al, added at factory)
Blue
Fire panel interface A – in
Violet
Fire panel interface B – out
Gray
Fire panel interface A – out
Blue/red
M-Bus
Max, 40 V, non-polarized
Gray/
pink
1
With series resistor, standard 680
Ω
Содержание ADICOS HOTSPOT-1000
Страница 36: ......