FAILURE
27
ADICOS HOTSPOT-1000
410-2410-001 EN11
8.4.2
Replacing the ADICOS HOTSPOT-1000
An old
ADICOS HOTSPOT-1000
has to be replaced when
– The serviceable life of the detector has been exhausted
– It is foreseeable that functioning will decline prematurely
– A change in the operating conditions requires a different type of detector
When the
ADICOS HOTSPOT-1000
is replaced, the parameter set from the previous device
can be imported if the following conditions are met:
– The detector is mounted in the same position.
– There is a data backup of the parameterization available.
– The detector is not being replaced because the build-
ing is to be used for a different purpose.
To replace the detector, deenergize the system and detach the old detector. Install the new
detector as described in this manual.
9 Failure
Failure of the
ADICOS HOTSPOT-1000
is indicated by the yellow signal LED lighting up as
well as by the “Failure” signal relay deenergizing.
The
ADICOS HOTSPOT-1000
recognizes the following states and causes of failure:
Failure
Description
Measure
Undervoltage /
current failure
Operating voltage falls be-
low 20 V (even only briefly).
Check supply voltage
and wiring; use a more
powerful or additional
power pack; self-resetting
Checksum ROM/EEPROM
The checksum is no longer
right after restart or reset.
Replace detector
Test failure
The ADICOS service
software was used to
trigger a false failure
for test purposes.
Cancel test failure with
ADICOS
service software
Sensor fault
The IR sensor is defective
Replace detector
Undertemperature
Failure is triggered below
the default temperature
limit (standard: -15 °C)
Use the detector heater or in-
sulate the device sufficiently
Use the
ADICOS
service software to precisely analyze the failure states!