GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page
93
DC-M9204
Innovation Manual
Call Point
X
0.0006
=
0.0018
=
DI-M9300
Digital Single Input
Module
X
0.00026
=
0.0005
=
DI-M9301
Digital Single Input
and Output Module
X
0.00028
=
0.0007
=
DI-M9319
Digital Zone Monitor
Module
X
0.00038
=
0.00039
=
DI-M9305
Digital Single Riser
Output Module
X
0.00026
=
0.0005
=
Total currents (Add above currents)
(A)
(B)
Battery Capacity Requirement
Battery (AH) = (Standby Current Total x Discharge Time) + (Alarm Current Total x Alarm
Time)
([STANDBY (A) ______] X [(24 Hours) _____]) + ([ALARM (B) ______] X [Alarm in Hr.]
_____) = (C) ______ (AH)
NAC and AUX interfaces should not exceed 2.5A, and the standby current of AUX
interface should not exceed 0.25A.
Battery Selection
Battery Size = Multiply (
C
) by 1.20 to derate battery.
PS-12380 (38 AH) and PS-12400 (40 AH) are the recommended Power-Sonic batteries
for use with this panel.
Use of alternative batteries may result in failure of the FACP to meet agency and
regulatory requirements, and may result in shortened battery life. Batteries should be
tested regularly, and replaced at least every three years. If the Battery Trouble indicator
activates, obtain required service.