GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page
45
4
Operations
4.1 Programming on FACP
Configurations and definitions can also be programmed directly on the FACP.
Clicking the button
inputs engineering password to enter
Panel Setup
menu (tree
diagram) as shown below Fig 4.1.
Fig 4.1
4.1.1 Basic Setting
Panel Configuration: in the
Basic Setting
menu, clicking
Panel Configuration
shows all cards integrated in the FACP on the right for users to set cards quantity by
manual.
Display Board: 1 (by default)
Main Board:
1 (by default)
Indicator Board: 1 (by default)
ZCP:
user defined (0 ~ 32)
PSU250:
1 (by default)
NAC Card:
1 (by default)
Loop Card:
user defined (1 ~ 4)
Slot:
Loop Card:1 (by default)
Clicking
Slot
enters the screen of Slot Definition as shown in Fig 4.2. In the menu, the
listed slots are corresponding to those five slots of mother board on the control panel.
Users can set types of cards such as: Single LoopCard, Double LoopCard, Network
Card, Modbus Card, DACR Card, None.