GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page
89
Built-in MCU can store 14 history messages.
Polling LED can be set to close.
2 levels smoke sensitivities programmable, complies with UL268. Heat part
complies with UL521.
DC-M9101 is a Conventional Combination Heat Photoelectric Smoke Detector. It can be
connected to the panel through I-M9301 addressable input module or DI-M9319 Digital
Zone Monitor Module.
C.1.4 Detector Bases
DZ-03 Base is used to mount I-9102(UL), I-9103(UL) detectors as their conductive base.
During installation, you can easily fix the base before connecting cables, and then twist
the detector onto the base.
DB-M01 Base is used to mount DI-M9101, DI-M9102
,
DI-M9103, DC-M9101 DC-M9102
and DC-M9103 detectors as their conductive base. During installation, you can easily fix
the base before connecting cables, and then twist the detector onto the base.
C.2 Manual Pull Stations
DI-M9204 Digital Manual Call Point can be connected to the panel directly to complete a
fire alarm system.
DC-M9204 is a non-Addressable Manual Call Point. It can be connected to the panel
through I-M9301 addressable input module or DI-M9319 Digital Zone Monitor Module.
C.3 Loop Isolators
In loop type fire alarm system, short circuit of part of the loop often affects normal
operation of the whole system. C-M9503/ DC-M9503 Loop Isolator and DC-M9504Base
Mount Isolator can disable the shorted part of loop from the whole system to ensure
normal operation of other parts and can easily find the location of the disabled part.
C.4 Control Modules
I-M9300/ DI-M9300 Addressable Input Module is used to receive normally open
switch signals from connected fire protection devices, and transmit the messages
back to the FACP.
I-M9301/ DI-M9301 Addressable Output Module can be connected on an SLC to
receive the start command from the FACP. When receiving the command, it will close
the output relay to output normally-open / normally closed contact signal and
illuminate the active indicator.
DI-M9305 Digital Single Riser Output Module can communicate with the panel. The
module is designed to switch on/off 24VDC power at its output.
DI-M9319 Digital Zone Monitor Module is designed to connect with conventional
detectors.