GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page
86
Programmable as resettable or non-resettable
Nominal operating voltage: 24VDC
Maximum standby current: 0.25A
Maximum signaling current: 2.5A (Shared by both NAC1 and NAC2/AUX)
End-of-
line resistor: 1kΩ (Part No. 30108576)
B.1.6 Relays
Three fixed relays: Alarm, Supervisory and Trouble.
Two programmable relays: RL2, RL3. These two relays can be programmed as
Alarm, Supervisory, Trouble or Disable.
Contact rating: 2.0A @ 30VDC (resistive), power limited.
B.1.7 Input
Maximum current: 1.7mA (short circuit)
B.1.8 CAN Network
Class A.
Maximum distance between two neighbor nodes is 2500m with 18AWG
(0.81mm²) or 3000m with 16AWG (1.32mm²).
Maximum 250 nodes for combination of CAN and Fiber-Optical Network.
B.1.9 Fiber-Optical Network
LC single-mode fiber.
Maximum distance between two neighbor nodes is 20000m.
Maximum 250 nodes for combination of CAN and Fiber-Optical Network.
B.2.0 Modbus Communication
– for supplementary use only
RS232/RS485/RS422 configurable.
Maximum distance is 3m from IFP4M FACP to the third party equipment.
B.2 Typical Configuration of SLCs
The typical configurations of SLCs include Intelligent Photoelectric Smoke Detector,
Intelligent Rate of Rise and Fixed Temperature Heat Detector, Digital Manual Call Point,
Addressable Input Module, Addressable Output Module and Loop Isolators. Refer to table
B.1 for maximum length of wires in different configurations.
Table B.1
Configuration 1
Configuration 2
Configuration 3
Configuration 4
No. of smoke
detectors
60
80
100
120
No. of heat
detectors
8
10
10
15