GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page
5
Notices
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES:
This product incorporates field-programmable software. In order for the product to comply
with the requirements in the Standard for Control Units and Accessories for Fire Alarm
Systems, UL 864, certain programming features or options must be limited to specific
values or not used at all as indicated below.
Program feature
or option
Permitted in
UL 864? (Y/N)
Possible settings
Settings permitted in
UL 864
Output type of
NACs
Y
Steady: a continuous output
with no coding.
March Time: 120 ppm
(pulse-per-minute) output.
Synch: a continuous output
with
synchronized pulse
signal.
Temporal: Temporal-3
pattern.
“Synch” - for
compatible strobes
and horns connected
to NAC1 or NAC2
“Temporal” - for
compatible bells
connected to NAC1 or
NAC2
Output type of
AUX
Y
AUX, AUX SYNC
“AUX SYNC” - for
DI-M9305 controlled
NAC solution
“AUX” - for 24Vdc
Auxiliary power output
NAC1 NAC2
silencing
Y
Silenceable,
Non-Silenceable
Silenceable
Cause & Effect
Delay
(Output module
delay)
Y
0
– 300 seconds
0 second - for
required fire signaling,
e.g. DI-M9305
controlled NAC
solution
0
– 300 seconds - for
supplementary
process controls.
Consult with AHJs for
permissible
applications.