![GSI Group 890-00583 Скачать руководство пользователя страница 73](http://html1.mh-extra.com/html/gsi-group/890-00583/890-00583_user-manual_2275188073.webp)
A
List of Terminals in the Main
Enclosure and Battery Enclosure
Each module, input, or output has its place on the system board. To ensure no false alerts or trouble occur,
connect all modules, inputs and outputs in the correct area.
Table A-1
Main enclosure terminals and usage
Terminal
Terminal
Board
Description
ZONE1
Sensor input terminals numbered 1 through 8. Each input has its own
return (AGND).
AGND1–2
ZONE2
ZONE3
AGND3–4
ZONE4
ZONE5
AGND5–6
ZONE6
ZONE7
AGND7–8
ZONE8
EXT. MIC +
Inputs for an external microphone.
EXT. MIC –
EXT. MIC SHIELD
SBI +
Serial bus interface communication bus. Wired between the main system
and optional expansion modules. Each module has the same four termi-
nals. The same terminals are wired to each other between all modules.
SBI COMM A
SBI COMM B
SBI –
PVX COMM A
PVX communication bus.
PVX COMM B
GND
12 VDC +
12 VDC power output for external sensors. Maximum 750 mA.
12 VDC –
AUX.
28 VDC power output for external sensors. Maximum 350 mA.
AUX. SUPPLY –
SIREN +
Outputs to connect a siren.
SIREN –
895–00677
Agri-Alert 128 Touch
73
Содержание 890-00583
Страница 6: ...NOTES 6 895 00677 Agri Alert 128 Touch...
Страница 14: ...NOTES 14 895 00677 Agri Alert 128 Touch...
Страница 26: ...NOTES 26 895 00677 Agri Alert 128 Touch...
Страница 54: ...Chapter 8 Configuring a 0 5 Volt Zone Type 54 895 00677 Agri Alert 128 Touch...
Страница 56: ...NOTES 56 895 00677 Agri Alert 128 Touch...
Страница 64: ...NOTES 64 895 00677 Agri Alert 128 Touch...
Страница 68: ...NOTES 68 895 00677 Agri Alert 128 Touch...
Страница 72: ...NOTES 72 895 00677 Agri Alert 128 Touch...
Страница 75: ...B Wiring Diagram with Terminals 895 00677 Agri Alert 128 Touch 75...
Страница 78: ...NOTES 78 895 00677 Agri Alert 128 Touch...
Страница 84: ......
Страница 88: ...NOTES 88 895 00677 Agri Alert 128 Touch...