Once the error has been corrected,
•
press the "Start/Stop" button to restart the pump.
– The pump returns to the state it was in before
the error occurred.
9.10.6 Changing the number of permissible error strokes
To change the number of permissible error strokes
during the start-up operation and during normal
dosing operation.
Fig. 63
Permissible error strokes
1. Open the service level.
2. Repeatedly press the "Menu/Info" button to
navigate in the service level until you reach menu
item "St:60" (error stroke during start-up
operation).
– The display shows "St" and the number of
currently defined error strokes that are
permissible during the start-up operation.
3. Use the "Up" and "Down" buttons to set the
number of permissible error strokes during the
start-up operation in the range between 1 and 99.
4. Press the "Start/Stop" button.
– Confirm the setting and go to menu item
"FE: 7".
– The display shows "FE" and the number of
currently defined error strokes that are
permissible during normal dosing operation.
5. Use the "Up" and "Down" buttons to set the
number of error strokes until the error message is
triggered during normal dosing operation in the
range between 3 and 99.
6. Press the "Start/Stop" button
– to confirm the new settings
– to exit the service level
– to open the first function level.
9.10.7 Calibrating the sensor after the sensor has
been replaced
Once a sensor has been replaced, the new sensor
must be calibrated to the ambient pressure.
Prepare the pump for the calibration:
1. Before screwing in the sensor, check that no
dosing liquid is left in the place where the
pressure sensor will be screwed in!
2. Screw in the new sensor with the correctly fitting
O-ring.
3. Screw the sensor plug into socket 2.
4. Unscrew the suction valve.
Note
If the cable is broken, the dosing
controller and pressure
control/pressure display functions are
not active. When the "Menu/Info"
button is pressed twice to display the
chamber pressure, only "— — —" is
displayed.
Note
If the sensor fault cannot be corrected
immediately and if the pump is to
continue to run without a sensor,
switch off the dosing controller
(flow:OFF) and pressure control
function (P:OFF).
TM
03
65
75
45
06
Stop
Start
Down
Up
Stop
Start
Down
Up
St:60
ERROR
FE: 7
ERROR
Menu
Info
Permissible error strokes
during start-up operation
Use the "Up" and "Down" buttons to set the
number of error strokes until the error
message is triggered during normal dosing
operation in the range between 3 and 99.
Use the "Up" and "Down" buttons to set the
number of permissible error strokes during
the start-up operation in the range between
1 and 99.
Service level
Number of error strokes
until the error message is
triggered