• See fig.
for logic and priority for the pump control, and note
that the control sources "Switch" and "Display" have higher
priority than Remote.
Fig. 27
Logic and priority for the pump control
• Active alarms and warnings:
– Pump1Alarms1 (register 00423 [bits])
– Pump1Alarms2 (register 00424 [bits])
– Pump1Alarms3 (register 00425 [bits])
– Pump1Warnings1 (register 00426 [bits])
– Pump1Warnings2 (register 00427 [bits])
– Pump1Warnings3 (register 00428 [bits]).
Display bar
The blue bar at the top of the screen is used to open and close
specific displays that can show specific data and change settings
of the pit control system.
The descriptions below refer to fig.
• The "Pit operation" button opens the "Pit operation" display.
• The "Pit status" button opens the "Pit status" display.
• The "Pump 1" and "Pump 2" buttons open the "Pump 1" and
"Pump 2" displays.
• The "Setup" button opens the display for showing and
changing all the pump control levels. It might look as shown
below.
• Overflow level: SetOverflowLevel (register 00121 [0.01 m]).
• High level: SetHighLevel (register 00122 [0.01 m]).
• Alarm level: SetAlarmLevel (register 00123 [0.01 m]).
• Dry-running level: SetDryRunningLevel (register 00124 [0.01
m]).
• Foam-draining level: SetFoamDrainingLevel (register 00125
[0.01 m]).
• Start levels for pumps 1 and 2:
– SetStartLevelPump1 (register 00126 [0.01 m])
– SetStartLevelPump2 (register 00128 [0.01 m]).
• Stop levels for pumps 1 and 2:
– SetStopLevelPump1 (register 00127 [0.01 m])
– SetStopLevelPump2 (register 00129 [0.01 m]).
• The "Event log" button opens the display for showing a
scrollable list of event records (alarms and warnings). The
event log in the CU 36X contains the 50 latest events with the
newest one at the top.
Each record takes up seven registers and has the following
format:
<ID> <Code> <Description> <Source> <Type> <Time stamp>
The complete event log takes up 7 x 50 = 350 registers and is
located in the register area register 06001 to 06351.
TM
04
36
80
48
08
Note
Before trying to operate the pumps, remember to
write the ScadaPinCode (register 00109) if PIN code
protection has been enabled.
Switch
Display
Remote
Automation
Stop
Stop
Stop
Stop
Start
Start
Start
Start
Auto
Auto
Auto
Pumping control levels
Overflow level
XXX cm
Cancel
Update
High level
XXX cm
Alarm level
XXX cm
Dry-running level
XXX cm
Foam-draining level
XXX cm
Pump 1
Pump 2
Start level
XXX cm
XXX cm
Stop level
XXX cm
XXX cm
Note
These registers only reflect the actual values if the
WriteSetup.ReadWriteSeparation (register 00006) bit
is set to 0. Otherwise, reading back the actual values
has to take place via the corresponding read-only
registers, e.g. OverflowLevel (register 00240).
Note
Before trying to change the settings, remember to
write the ScadaPinCode (register 00109) if PIN code
protection has been enabled.