English (GB)
21
00132
SetStartLevelPump4
0.01 m
Setting a new start level, pump 4.*
00133
SetStopLevelPump4
0.01 m
Setting a new stop level, pump 4.*
00134
SetStartLevelPump5
0.01 m
Setting a new start level, pump 5.*
00135
SetStopLevelPump5
0.01 m
Setting a new stop level, pump 5.*
00136
SetStartLevelPump6
0.01 m
Setting a new start level, pump 6.*
00137
SetStopLevelPump6
0.01 m
Setting a new stop level, pump 6.*
00138
SetCurrentMaxAlarmGrp1
0.01 A
Set current max. alarm for group 1*
00139
SetCurrentMinAlarmGrp1
0.01 A
Set current min. alarm for group 1*
00140
SetCurrentMaxWarnGrp1
0.01 A
Set current max. warning for group 1*
00141
SetCurrentMinWantGrp1
0.01 A
Set current min. warning for group 1*
00142
SetCurrentMaxAlarmGrp2
0.01 A
Set current max. alarm for group 2*
00143
SetCurrentMinAlarmGrp2
0.01 A
Set current min. alarm for group 2*
00144
SetCurrentMaxWarnGrp2
0.01 A
Set current max. warning for group 2*
00145
SetCurrentMinWantGrp2
0.01 A
Set current min. warning for group 2*
00146
SetSetpointPump1
0.1 %
Set PID control loop setpoint for pump 1*
00147
SetSetpointPump2
0.1 %
Set PID control loop setpoint for pump 2*
00148
SetSetpointPump3
0.1 %
Set PID control loop setpoint for pump 3*
00149
SetSetpointPump4
0.1 %
Set PID control loop setpoint for pump 4*
00150
SetSetpointPump5
0.1 %
Set PID control loop setpoint for pump 5*
00151
SetSetpointPump6
0.1 %
Set PID control loop setpoint for pump 6*
00152
SetControlModePump1
enum
Set control mode for pump 1:
0 = Fixed Frequency
1 = Linear Control
2 = Minimum Control
3 = PID control*
00153
SetControlModePump2
enum
Set control mode for pump 2:
0 = Fixed Frequency
1 = Linear Control
2 = Minimum Control
3 = PID control*
00154
SetControlModePump3
enum
Set control mode for pump 3:
0 = Fixed Frequency
1 = Linear Control
2 = Minimum Control
3 = PID control*
00155
SetControlModePump4
enum
Set control mode for pump 4:
0 = Fixed Frequency
1 = Linear Control
2 = Minimum Control
3 = PID control*
00156
SetControlModePump5
enum
Set control mode for pump 5:
0 = Fixed Frequency
1 = Linear Control
2 = Minimum Control
3 = PID control*
00157
SetControlModePump6
enum
Set control mode for pump 6:
0 = Fixed Frequency
1 = Linear Control
2 = Minimum Control
3 = PID control*
00158
SetFeedbackSensorTypePump1
enum
Sets the feedback sensor type for pump 1:
4 = Flow rate
5 = Level, pressure
6 = Level, Ultrasound
13 = User defined Sensor 1
14 = User defined sensor 2
15 = User defined sensor 3*
00159
SetFeedbackSensorTypePump2
enum
Sets the feedback sensor type for pump 2:
4 = Flow rate
5 = Level, pressure
6 = Level, Ultrasound
13 = User defined Sensor 1
14 = User defined sensor 2
15 = User defined sensor 3*
Address
Register name
Scale
Description