English (GB)
46
9.14 Alarm simulation register block
9.15 User register block
9.16 Name string register block
Address
Register name
Scale
Description
00701
SimulationEventCode
enum
Event code to simulate.
00702
SimulationEventSource
enum
Event source to simulate.
00703
SimulationEventDeviceNo
enum
Event device number to simulate.
00704
SimulationEventActionType
enum
0 = Warning
1 = Alarm
2 = Disabled.
00705
SimulationActivate
Bool
Activation of simulation features.
0 = Deactivate simulation
1 = Activate simulation.
00706
SimulationStatus
Bit 0: SimulationActive
Bool
State of simulation.
0 = Not active
1 = Active.
Address
Register name
Scale
Description
00751-00800 UserRegisters
Unscaled
This area is for device labelling by the user. Neither the
CU 36X nor the CIM will modify this area.
The user area values are stored in the device and will
remain after a power-off.
Address
Register name
Scale
Description
00801-00920 NameRegisterArea
UTF-8 chars.
Name string read from the Dedicated Controls CU 36X.
UTF-8 is a variable-length character encoding for
Unicode. It can represent any character in the Unicode
standard.
It may take up to 60 seconds for a change to be visible.