English (GB)
23
* If ReadWriteSeparation (register 00006, bit 0) is set to "0", the CIM will overwrite this register value with the resulting level.
00176
SetFixedFrequencyPump1
Hz
Fixed frequency for pump 1*
00177
SetFixedFrequencyPump2
Hz
Fixed frequency for pump 2*
00178
SetFixedFrequencyPump3
Hz
Fixed frequency for pump 3*
00179
SetFixedFrequencyPump4
Hz
Fixed frequency for pump 4*
00180
SetFixedFrequencyPump5
Hz
Fixed frequency for pump 5*
00181
SetFixedFrequencyPump6
Hz
Fixed frequency for pump 6*
00182
SetH2SLevel
1 ppm
For reception of Hydrogen sulfide (H2S) measurement via GRM
00183
SetH2SSensorFaults
Bit 0: SignalFault
Bool
For reception of H2S sensor signal fault via GRM
0 = No fault
1 = Sensor signal fault
00184
SetDosingRef
0.1 litre/h
Set chemical dosing reference for H2S level control
Address
Register name
Scale
Description