English (GB)
48
9.18 Event log register block
The event log contains the latest 50 event entries. Each entry
consists of seven registers, containing information about the
event.
Address
Register name
Scale
Description
06001
NoOfEventsInLog
Unscaled
Number of events in the event log.
06002
EventIDLog1
Unscaled
Event ID for logged event No 1.
06003
EventCodeLog1
enum
Event code for logged event No 1.
06004
EventSourceLog1
enum
Event source for logged event No 1.
0 = System
1 = CU 36X
2 = IO 351B
3 = IO 111, pump
4 = MP 204, pump
5 = Analog input
6 = Pump
7 = Add-on CIM module
8 = Battery/UPS
9 = Mixer
10 = Analog input, level sensor
11 = Analog input, flow sensor
12 = Analog input, power sensor
13 = Analog input, user-defined sensor
14 = CUE (variable-frequency drive).
06005
EventDeviceNo
Unscaled
Device number related to the event or its recognition.
0 = No related number
1 = Value of related number, pump 1
2 = Value of related number, pump 2
3 = Value of related number, pump 3
4 = Value of related number, pump 4
5 = Value of related number, pump 5
6 = Value of related number, pump 6.
06006
EventTypeAndConditionLog1
enum
Event type and condition of logged event No 1.
0 = -
1 = Alarm condition appears
2 = Alarm condition disappears
3 = Warning condition appears
4 = Warning condition disappears.
06007
EventTimeStampLog1HI
1 second
Seconds since midnight January 1st 1970 (UNIX time).
06008
EventTimeStampLog1LO
06009-06344 Event log 2…49
-
-
06345
EventIDLog50
Unscaled
Event ID for logged event No 50.
06346
EventCodeLog50
enum
Event code for logged event No 50.
06347
EventSourceLog50
enum
Event source for logged event No 50.
06348
EventDeviceNo
Unscaled
Device number related to the event or its recognition.
06349
EventTypeAndConditionLog50
enum
Event type and condition of logged event No 50.
06350
EventTimeStampLog50HI
1 second
Seconds since midnight January 1st 1970 (UNIX time).
06351
EventTimeStampLog50LO
Pumpland.ru