14 / 116
00CNO0192-E (U0627512)
CONDENSINOX -
Installation, Use and Maintenance
3.3.
Conditions of use
MODEL
40
50
60
80
100
Maximum starting temperature setpoint
°C
80
Max starting temperature
°C
85
Safe temperature
°C
106
Max service pressure
hPa (bar)
4000
(4)
Minimum cold pressure
hPa (bar)
1000
(1)
Hydraulic pressure loss at ∆T 20
daPa
160
350
350
210
300
Nominal water flow rate (P/20)
m
3
/h
1.7
2.15
2.6
3.4
4.2
Maximum water flow rate (P/10)
m
3
/h
3.4
4.3
5.2
6.8
8.4
Water capacity
L
94
88
88
136
130
Weight without water
kg
134
140
140
215
225
Room temperature (min/max)
°C
5 / 45
Room relative humidity
5% to 95%
Level of protection
IP20
Maximum installation altitude
m
2000
3.4. Electrical connection
MODEL
40
50
60
80
100
Electrical power supply
V
230 V AC (+10% -15%), 50Hz
Electrical power consumption
at Qn (excluding accessories)
W
120
142
160
210
280
Electrical power consumption
in standby mode
W
5
Maximum length of sensor cables
m
Hot water sensor: 10
Outdoor sensor: 40 at 0.5 mm² (120 at 1.5 mm²)
Room thermostat: 200 at 1.5 mm²
Room sensor: 200 at 1.5 mm²
Terminal output power
V
230 V AC (+10%, -15%)
A
5 mA at 1 A