CONDENSINOX -
Installation, Use and Maintenance
MB DB
}
LPB Bus
L2
N L3
N
L3 L1
N
QX2
QX3
QX1
230 VAC 50 Hz
power supply
}
}
D. SPECIFIC START-UP PROCEDURE
"
Fit and connect the accessories.
"
Start up the boiler alone.
"
Make the following adjustments:
On boiler no. 1: master
Line No. Value
• Menu
Time and date
Set the time
Hour / minute (1)
HH.MM
Set the date
Day / month (2)
DD.MM
Set the year
Year (3)
YYYY
• Menu
Configuration
Configure the isolation valve Q1.1
Relay QX3 output (5892)
Boiler pump Q1
Configure the cascade flow sensor B10:
Sensor input BX2 (5931)
Common flow
sensor B10
For a request via 0…10V input
Configure input H1
H1 input function (5950)
Request consum.
circ.1 10V
H1 voltage value 1 (5953)
0.0
Alarm relay
Isolation
valve Q1.2
Diagram: CX10