CONDENSINOX -
Installation, Use and Maintenance
Line No. Value
• Menu
Domestic Hot Water
Configure an anti-legionella function
Anti-legionella function (1640)
- - -
Periodic legionella function (1641)
- - -
Weekday Legionella function (1642)
- - -
Anti-legionella temperature setpoint (1645)
- - -
Anti-legionella function duration (1646)
- - -
Maintenance optimisation:
It is possible to generate a maintenance message that does not cause a boiler fault. This maintenance
message can occur after the 3 following counters reach set values:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Hours of burner operation (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is advisable to use
at least parameter 7044 for annual maintenance.
G. ROOM SENSOR CONFIGURATION
Link each sensor to a heating circuit:
•
User interface
menu for
each room sensor
Configure the room sensor with a heating circuit
Use (40)
Room appliance 1,
2 or 3
Each room sensor allows its heating circuit to be configured. Room sensors 1, 2 and 3 adjust
parameters 712 (heating circuit 1), 1012 (heating circuit 2) and 1312 (heating circuit 3) respectively.