CONDENSINOX -
Installation, Use and Maintenance
Line No. Value
H1 function value 2 (5956)
1000 (for
equivalence
10 V = 100°C)
Diagram: CX3
page 3 / 3
Line No. Value
For a request via LPB
• Menu
LPB network
Check that the boiler is defined as the
master generator
Appliance address (6600)
1
Segment address (6601)
0
Bus supply function (6604)
Automatic
Clock operation (6640)
Slave with
adjustment
E. ELECTRICAL AND HYDRAULIC VALIDATION
For a request via 0…10V input
• Menu
Input/output test
H1 voltage
H1 voltage signal (7840)
To be confirmed
against the voltage
sent by the boiler
room controller
For a request via LPB
If the boiler room regulator is configured as the master clock, the boiler
controller must retrieve the date and time.
F. OPTIMISING THE SETTINGS
Maintenance optimisation:
It is possible to generate a maintenance message that does not cause a boiler fault. This maintenance
message can occur after the 3 following counters reach set values:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Hours of burner operation (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is advisable to use
at least parameter 7044 for annual maintenance.
Warning
the boiler considers a heat demand for a voltage H1> 0.2 V and a resulting setpoint> 6 ° C *
The boiler no longer considers a heat demand for a voltage H1 <0.2V or a resulting setpoint <4 ° C *
In this second case, the boiler isolation valve will close. If the installation does not include a hydraulic
decoupling bottle, all the network pumps must be stopped at the risk of causing them to cavitate..
* : according to the scale entered in the parameter "5956"