72 / 116
00CNO0192-E (U0627512)
CONDENSINOX -
Installation, Use and Maintenance
F. OPTIMISING THE SETTINGS
On master and slave boilers
Heating circuit optimisation:
Diagram: CX11
page 9 / 10
• Menu
Heating circuit 1/2/3
Adjust the low setpoint
Low setpoint temperature (712/1012/1312)
- - -
• Menu
HC1/HC2/HC3 timer program
Preselection
Preselection (500/520/540)
- - -
Adjust the programmed times
On/off phases (501...506)
(521...526)
(541...546)
- - -
• Menu
HC1/HC2/HC3 holidays
Preselection
Preselection (641/651/661)
- - -
Adjust the programmed times
On/off phases (642-643)
(652-653)
(662-663)
- - -
• Switch the heating program to automatic
AUTO
DHW optimisation:
N° Ligne
Valeur
• Menu
Domestic Hot Water
Adjust the low setpoint
Low setpoint (1612)
- - -
Set the DHW release program
DHW release (1620)
Timer prog.4/DHW
•
Configuration
menu
Activate the heating circuits' frost
protection mode
Frost protection plant (6120)
On
• Menu
Timer program 4/DHW
Preselection
Preselection (560)
- - -
Adjust the programmed times
On/off phases (561...566)
- - -