30
6.9.5 RJ45 Connection
RJ45 is specifically employed here for LAN/WLAN via which inverter web page
can be easily accessed. Refer to figures below and on P.25 for RJ45 wiring. Make
sure that RJ45 cable is wound through the brown EMI core (from accessary kit)
with 4 turns each, as for noise immunity
6.9.6 Connecting GFCI Buzzer (Optional)
Buzzer is used to alert user when ground fault current interrupter (GFCI) is
active. It’s also known as residual current monitoring unit (RCMU).
1.
Insert extension cord through the M20 cable gland and connect to
designated socket on inverter, as illustrated below and on P.25
2.
Attach and fix the buzzer on an
indoor
surface such as a wall
3.
Connect buzzer with extension cord
4.
If the length of cord is not enough, please trim and extend with some
similar cord to desired length
PV-5000T-U/PV-8000T-U/PV-10000T-U
PV-15000T-U/PV-20000T-U
Place the Buzzer Where You Can Hear
The buzzer will notice you in case of ground current fault.
Place it near you. Do not put in a cabinet or place far away.
Extension Cord for Buzzer
RJ45 Cable for Internet
Extension Cord for Buzzer
RJ45 Cable for Internet
Содержание PV-10000T-U
Страница 12: ...11 5 4 Product Labels ...
Страница 14: ...13 6 2 Unpacking PV 15000T U ...
Страница 15: ...14 6 3 1 Unpacking PV 20000T U ...
Страница 16: ...15 6 3 2 Unpacking PV 20000T U E Display ...
Страница 17: ...16 6 4 Assembly Chart PV 5000T U PV 8000T U PV 10000T U PV PV15000T U ...
Страница 18: ...17 6 5 Assembly Chart PV 20000T U ...
Страница 81: ...80 14 Addendum 14 1 Efficiency Charts 14 1 1 PV 5000T U 14 1 2 PV 8000T U ...
Страница 82: ...81 14 1 3 PV 10000T U 14 1 4 PV 15000T U ...
Страница 83: ...82 14 1 5 PV 20000T U ...
Страница 84: ...P N MUB0 A00000 0 ...