background image

8

1.  With the softener in the bypass mode 

(Fig. 2 on page 2)

 and the control valve in normal operation 

where the display shows either the time of day or the gallons remaining:   

 

Manually add 3 GALLONS of water to the regenerant tank.

    

 

NOTE:

 If too much water is put into the brine tank during softener start up it could result in a salty water 

complaint after the first regeneration.

     During the first regeneration the unit will draw out the initial volume of brine/regenerant and refill it with 

the correct preset amount.

2.  Press and hold the 

regeN

 button until the motor starts (3 seconds). Release button. The display will either 

read 

backwash

 or 

fill

 and the remaining time in this step is counting down. If 

backwash

 is shown in 

window, proceed to step 2b.

 

 

2a.

 If the unit display is 

fill

, check to verify that the regenerant tank is filling at a rate of 1/2 gallon 

per minute. Check Brine line connections for leaks. Press 

regeN

 button and unit will proceed to the 

softeNiNg

 position. During a normal regeneration this will be a 4 hour period for salt to dissolve. 

Press 

regeN

 again to put valve in BACKWASH. Proceed to 2b.

 

 

2b.

 Unplug the transformer so that the valve will not cycle to the next position. Open the inlet handle 

of the bypass valve

 

very slightly

 allowing water to fill the tank 

slowly

 in order to expel air. Once 

air is expelled and water is running at drain, open inlet to control and place into the diagnostic 

mode 

(Fig. 3 on page 2)

.

CAUTION: If water flows too rapidly, it could result in loss of media to 

the drain. When the water is flowing steadily to the drain without the 

presence of air, slowly open the inlet valve. Check drain that it can 

receive the flow of water. Restore power.

3.   Press 

regeN

 button again to put the valve into BRINE position. Check the brine line for suction (after unit is 

full). Verify that water is being drawn from regenerant tank with no air leaks or bubbles in the brine line. 

There should be a slow flow to the drain.

4.  Press 

regeN

 button again and place unit into a second BACKWASH position. Water will flow steadily at the 

drain. Check for the presence of air. Again, check drain that it can receive the flow of water. 

 

5.   Press 

regeN

 button and place unit into rinse position. Check drain line to be secure and that drain can 

receive the flow of water. There should be a rapid flow to the drain. Unplug transformer to keep the 

valve in the RINSE position. Allow to run until steady, clear and without air. While the unit is rinsing, 

load the brine tank with water softener salt.   

 

6. Press the 

regeN

 button.

 

 

6a.

 For units that “Pre Fill” the brine tank, the valve will cycle back to the normal operating position. 

Advance to Step 8.     

 

 

6b

.

 For units that “Post Fill,” the unit is now in the FILL position. Check to verify that the  

regenerant tank is filling at a rate of 1/2 gallon per minute. Check Brine line connections for leaks. 

Proceed to Step 7.

7.  Press 

regeN

 button again. Valve will cycle back to the normal operating position with the time of day or 

gallons remaining displayed.

 

s

TarT

-

uP

 i

nsTruCTions

 

for

 W

aTer

 s

ofTeners

:

Содержание GACS1035

Страница 1: ...Water Technologies Water Technologies Water Technologies Installation Instructions Owner s Manual Advance Cabinet Series Softeners...

Страница 2: ...Solids Over 10ppm may be harmful for human consumption Water conditioners do not remove nitrates or coliform bacteria this requires specialized equipment Greenway Water Conditioners are precision bui...

Страница 3: ...the exit are incorporated If desired two regenerations within 24 hours are possible with a return to the preset program To do a double regeneration 1 Press the regen button once regen today will flas...

Страница 4: ...to the building while not allowing water to exit from the system to the building Fig 3 This allows the service technician to draw brine and perform other tests without the test water going to the buil...

Страница 5: ...be used to unscrew the nut or cap Do not use a pipe wrench to tighten nuts or caps Do not place screwdriver in slots on caps and or tap with a hammer SITE REQUIREMENTS water pressure 30 100 psi curre...

Страница 6: ...f the control valve form a 7 loop at the discharge end of the line so that the bottom of the loop is level with the drain connection on the control valve This will provide an adequate anti siphon trap...

Страница 7: ...ss as calcium carbonate per gallon using the s or t buttons The default is 20 with value ranges from 1 to 150 in 1 grain increments Note The grains per gallon can be increased if soluble iron needs to...

Страница 8: ...amming cont d 3 Manual Regeneration Sometimes there is a need to regenerate the system sooner than when the system calls for it usually referred to as manual regeneration There may be a period of heav...

Страница 9: ...ne tank filling and at no time during this process will you be without treated water 4 Power Loss If the power goes out for less than two hours the system will automatically reset itself If an extende...

Страница 10: ...de Fig 3 on page 2 CAUTION If water flows too rapidly it could result in loss of media to the drain When the water is flowing steadily to the drain without the presence of air slowly open the inlet va...

Страница 11: ...ay be needed for correct operation 2 Iron removal may vary depending on form of iron pH and other local conditions On waters that are pre chlorinated or where other pre oxidation occurs an iron precip...

Страница 12: ...ation time option in programming E control set at NORMAL on 0 E check with regeneration time option in programming 5 Error followed by code Error code 1001 unable to recognize start of regeneration Er...

Страница 13: ...and PC board power B no power at outlet B restore power C broken drive gear or drive cap assy C replace gear or drive cap assy D defective PC board D replace board 8 Valve does not regenerate automati...

Страница 14: ...o Part No Description Qty 1 YY WS CV3005 Spacer stack assembly 1 2 YY WS CV3004 Drive cap assembly 1 3 YY WS CV3135 O ring 228 1 4a YY WS CV3011 Piston assembly downflow 1 4b YY WS CV3011 01 Piston as...

Страница 15: ...ng 013 lower The injector plug and the injector each use one lower and one upper o ring REFILL PORT ASSEMBLY Item No Part No Description Qty 1 YY WS CV3195 01 Refill port plug assembly 1 2 YY WS CH461...

Страница 16: ...CV3162 010 1 0 DLFC for 3 4 elbow YY WS CV3162 013 1 3 DLFC for 3 4 elbow YY WS CV3162 017 1 7 DLFC for 3 4 elbow YY WS CV3162 022 2 2 DLFC for 3 4 elbow YY WS CV3162 027 2 7 DLFC for 3 4 elbow YY WS...

Страница 17: ...3 01 Meter plug assembly 1 SAFETY FLOAT ASSEMBLY Item No Part No Description 1 YY WS CH4650 01 474 safety elbow 3 8 2 YY WS CH4655 474 5 gpm flow control 3 YY WS CH4615 Elbow locking clip 4 YY WS CH46...

Страница 18: ...connect 2 2 YY WS CV3150 Split ring 2 3 YY WS CV3105 O ring 215 2 4 YY WS CV3145 Bypass rotor 1 2 5 YY WS CV3146 Bypass cap 2 6 YY WS CV3147 Bypass handle 2 7 YY WS CV3148 Bypass rotor seal retainer...

Страница 19: ...WS CV3189 Fitting 2 1 BRASS SWEAT Item No Part No Description Qty YY WS CV3007 02 1 brass sweat assembly 2 1 YY WS CV3151 Nut 1 quick connect 2 2 YY WS CV3150 Split Ring 2 3 YY WS CV3105 O ring 215 2...

Страница 20: ...teps as shown to the right To access this mode press set clock 1 Accessed by pressing set clock 2 Adjust hours with and buttons AM PM toggles at 12 3 Press next 4 Adjust minutes with and buttons 5 Pre...

Отзывы: