Kitchen Fan Control Center

®

Installation

Control Box Mounting

Locate an area with enough space to mount the control 
box and fasten to the wall . Use appropriate type 
fasteners depending on the mounting location . Avoid 
installing the control box in environments with high 
magnetic and/or radio frequency interference .

NOTE

Control box may be factory mounted . If so, continue 
to the next section .

Switch Mounting

Locate an area with enough space to mount the 
switches junction box and fasten to the wall .

NOTE

If the switches were NOT shipped loose, provided in a 
separate junction box, continue to the next section .

Temperature Sensor(s) - Hood Mounting

NOTE

Temperature sensor(s) will be provided only if the 
digital temperature interlock option was configured/
ordered with the unit . If it wasn’t, continue to the next 
section .
Temperature sensor(s) may be factory installed . If so, 
continue to the next section .

2 . Find a spot for the sensor in the flat space that will 

not interfere with the fire suppression nozzles and 
that is not within 12 inches (304 .8 mm) of any light 
fixtures . Cut a 3/4 to 7/8-inch (19 .0 to 22 .2 mm) 
diameter hole in the flat spot of the capture tank .

1 . Locate flat area(s) at the top interior of the hood in 

front of the filters, towards the front of the hood .

CAD Drawing from Tyler Schilling
Emailed to Barb on March 22, 2011
Updated the PN of the Resistive Temperature Detector to 384925 as provided in edits from Aaron Van Krey - October 18, 2012
Updated the for the Digital Temperature Interlock IOM - edits provided by Aaron Van Krey - November 20, 2016

Octagon Extension
PN 830125

Lock Washer

Nut

Compression Seal
PN 463570

Gasket

J-Box Plate
PN 732396

Temperature Sensor
PN 384925

Octagon Cover
PN 380926

2 inch typical

(50.8 mm)

19.525 inches

(495.9 mm)

3 inch air space

(76.2 mm)

Additional Octagon Extension
(Optional)
PN 830125

0.75 to 0.875 inch 

(19.0 to 22.2 mm)

diameter hole

Hood Surface

1

2

3

1.

PLACE THE J-BOX PLATE INSIDE OF THE OCTAGON EXTENSION  

RING, AND PLACE OVER HOLE.

2.

DISASSEMBLE THE COMPRESSION SEAL AND PLACE THROUGH 

THROUGH HOLE AND J-BOX PLATE AS SHOWN. TIGHTEN THE NUT 

INSIDE THE OCTAGON EXTENSION RING.

1.

PLACE THE THERMOSTAT THROUGH THE COMPRESSION 

COMPRESSION SEAL AND TIGHTEN THE COMPRESSION FITTING. 

2.

INSTALL THE COVER FOR THE OCTAGON BOX.

CUT A 0.75" - 0.875" HOLE IN THE FLAT SPOT OF THE 

CAPTURE TANK OF THE HOOD. KEEP 12" AWAY FROM 

ANY LIGHT FIXTURE.

Sensor Install

(cutout area)

Exhaust Area

Supply Area

(optional)

HOOD PLAN VIEW

P.O.BOX 410 SCHOFIELD, WISCONSIN 54476-0410

TITLE

DRAWN BY

ECO

B

ENG. REF.

DATE

SUPERSEDES

SCALE

CAD DRAWING NO.

MROCZENSKI_L

12/02/2009

1/4

IAN29890

INSTR, ADJ. TEMP 

INTERLOCK IN FLAT 

SPOT

Top View of Exhaust Hood

CAD Drawing from Tyler Schilling
Emailed to Barb on March 22, 2011
Updated the PN of the Resistive Temperature Detector to 384925 as provided in edits from Aaron Van Krey - October 18, 2012
Updated the for the Digital Temperature Interlock IOM - edits provided by Aaron Van Krey - November 20, 2016

Octagon Extension
PN 830125

Lock Washer

Nut

Compression Seal
PN 463570

Gasket

J-Box Plate
PN 732396

Temperature Sensor
PN 384925

Octagon Cover
PN 380926

2 inch typical

(50.8 mm)

19.525 inches

(495.9 mm)

3 inch air space

(76.2 mm)

Additional Octagon Extension
(Optional)
PN 830125

0.75 to 0.875 inch 

(19.0 to 22.2 mm)

diameter hole

Hood Surface

1

2

3

1.

PLACE THE J-BOX PLATE INSIDE OF THE OCTAGON EXTENSION  

RING, AND PLACE OVER HOLE.

2.

DISASSEMBLE THE COMPRESSION SEAL AND PLACE THROUGH 

THROUGH HOLE AND J-BOX PLATE AS SHOWN. TIGHTEN THE NUT 

INSIDE THE OCTAGON EXTENSION RING.

1.

PLACE THE THERMOSTAT THROUGH THE COMPRESSION 

COMPRESSION SEAL AND TIGHTEN THE COMPRESSION FITTING. 

2.

INSTALL THE COVER FOR THE OCTAGON BOX.

CUT A 0.75" - 0.875" HOLE IN THE FLAT SPOT OF THE 

CAPTURE TANK OF THE HOOD. KEEP 12" AWAY FROM 

ANY LIGHT FIXTURE.

Sensor Install

(cutout area)

Exhaust Area

Supply Area

(optional)

HOOD PLAN VIEW

P.O.BOX 410 SCHOFIELD, WISCONSIN 54476-0410

TITLE

DRAWN BY

ECO

B

ENG. REF.

DATE

SUPERSEDES

SCALE

CAD DRAWING NO.

MROCZENSKI_L

12/02/2009

1/4

IAN29890

INSTR, ADJ. TEMP 

INTERLOCK IN FLAT 

SPOT

Содержание KFCC

Страница 1: ...FCC Field Connection Checklist 16 General Wiring Diagram 17 Testing 18 Operation 19 Troubleshooting 19 Maintenance 20 Frequently Asked Questions 20 Replacement Parts 21 Codes and Standards 21 Maintena...

Страница 2: ...with additional relays prewired to the fan starter s These additional relays are capable of turning on the kitchen exhaust and shutting down supply regardless of the present state of the fans via inte...

Страница 3: ...Octagon Extension Optional PN 830125 0 75 to 0 875 inch 19 0 to 22 2 mm diameter hole Hood Surface 1 2 3 1 PLACE THE J BOX PLATE INSIDE OF THE OCTAGON EXTENSIO RING AND PLACE OVER HOLE 2 DISASSEMBLE...

Страница 4: ...96 Temperature Sensor PN 384925 Octagon Cover PN 380926 2 inch typical 50 8 mm 19 525 inches 495 9 mm 3 inch air space 76 2 mm Additional Octagon Extension Optional PN 830125 0 75 to 0 875 inch 19 0 t...

Страница 5: ...tension PN 830125 Junction Box Plate PN 732396 19 525 inches 495 9 mm 3 inch air space 76 2 mm 2 inch typical 50 8 mm Exhaust Area Exploded View Components 2 inches 50 8 mm Hood Exhaust Collar front s...

Страница 6: ...t will need to be run to the panel as well to power the lights The KFCC can provide up to three light circuits Power for Hood Lights 115 VAC 15 amp circuit to terminals H2 and N2 first light circuit 1...

Страница 7: ...ections to Starters and Fans Fire System Integration Two Fire System Microswitches C NO BK YW NC FS1 BR BK C NO BK YW NC FS2 RD RD BR BK C1 NC1 NO1 G NOTE C2 NC2 and NO2 terminals are provided for a s...

Страница 8: ...WH S1 S1 S1H S1 S1H S1 Factory mounted switch Factory wiring to switch R LT1 S1N S1 S1H S1 S 1 B2 H2 R CONNECTIONS TO Remote Mounted Switch TEMPERED MUA FAN S1 LO S1 HI S1S S1F Two Fire System Micros...

Страница 9: ...Tempered Supply Heat Only To terminals R and W1 Tempered Supply Cool Only To terminals R and Y1 Tempered Supply Heat and Cool To terminals R common W1 heat and Y1 cool Connections from these terminals...

Страница 10: ...t wiring should be followed Please see either Switches Optional Lights on page 8 or Combination Light Fan Switch on page 9 for additional wiring information NOTE For lights out in fire option light ci...

Страница 11: ...T3 A T3 B TS3 LT SL3 SL4 115V STATUS LIGHT Status Lights Optional The option adds status lights to the face of the KFCC Power will have to be provided for each light in the field Status light s Bring...

Страница 12: ...al Temperature Interlock Thermostat Optional NONE EXHAUST AIR FLOW SWITCH FIELD WIRED T1 B T1 A TS1 TC1 2 1 3 11 12 4 T2 A T2 B TS2 T3 A T3 B TS3 LT SL3 SL4 115V STATUS LIGHT NOTE Do not connect tempe...

Страница 13: ...o store value 4 Press OUT1 OUT2 C F Set Set A U X OUT1 OUT2 C F Set Set A U X buttons together to exit set point menu or wait 1 minute Show Sensor Values Press OUT1 OUT2 C F Set Set A U X OUT1 OUT2 C...

Страница 14: ...ime Minutes 0 0 0 0 0 0 c23 Minimum Output 3 On Time Minutes 0 0 0 0 0 0 c31 On Time Fault Sensor 1 Cycle Minutes 1 0 1 0 1 0 c32 On Time Fault Sensor 2 Cycle Minutes 0 0 1 0 1 0 c33 On Time Fault Sen...

Страница 15: ...adjusted slightly depending of both ambient and cooking conditions The adjustment knob is located on the back of the thermostat Use a small blade screwdriver to make the adjustments 1 Turn countercloc...

Страница 16: ...y be directly wired to hood lights Thermal heat only terminals R W1 Thermal cool only terminals R Y1 Thermal heat and cool terminals R W1 Y1 MUA Interface if equipped To MUA Control Center terminals R...

Страница 17: ...WH closed w power at H1 N1 fire system armed open w power at H1 N1 fire system armed can be used for shunt trip alarms etc Spare Relay Contacts closed on fire or no power open on fire or no power 22 2...

Страница 18: ...cation of fan start up shut down cooking equipment The fan switch should still be in the off position Once cooking equipment has cooled the thermostat will open triggering the timer function in the ti...

Страница 19: ...with temperature interlock either thermostat style or digital style Check wiring to control panel With thermostat style interlock thermostats must be wired in parallel With digital style interlock sen...

Страница 20: ...ans to prevent fan on off cycling while the temperature in the exhaust duct can reach steady state Without the delay cycling could occur both on startup or shutdown of cooking equipment The delay is t...

Страница 21: ...perature Sensor RTD Dwyer TE IBN E0448 00 880601 Temperature Controller Programmed for 1 sensor Dwyer TSDIN 013 G 880602 Temperature Controller Programmed for 2 sensors Dwyer TSDIN 013 G 880603 Temper...

Страница 22: ...______________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ______________________...

Страница 23: ...______________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ______________________...

Страница 24: ...anties Greenheck s Kitchen Ventilation Systems Controls and Energy Management catalog provides additional information describing the equipment fan performance available accessories and specification d...

Отзывы: