17

Kitchen Fan Control Center

®

General Wiring Diagram

This is an example of a generic wiring diagram of a KFCC . The KFCC is configured with  

two exhaust fans and one supply fan, as well as three digital interlock sensors .  

To see your job specific drawing, look on the inside panel of the KFCC .

CONTROL PANEL

Installation Location:

Ship Loose

"HEAT/COOL" SWITCH

"FAN" SWITCH

"LIGHTS" SWITCH

OFF

FAN

HEA

T

LIGH

TS

COOL

Volt

Gas Off w/Fans

Qty. Temp. Switches (0-1)

Remote Switches

Tempering SW

TERMINAL BLOCKS = 8 LB.IN

GROUNDING BLOCKS = 8 LB.IN

STB

AF

Wiring Diagram Code:

D
EC

PB

SV

ST

S

LT

G

FS

EF

SF
OL 

C

R

Audible Alarm

Gas Reset

Power for Gas Solenoid

Power for Shunt Trip

Heat Switch

Cool Switch

AD Switch

One Switch for L & F

Qty. Light Switches (0-3)

Qty. Fan Switches (0-3)

Hood Mark(s):

Fan Mark

Motor

HP

Panel Mark:

OR - orange

YW - yellow

WH - white

RD - red

PR - purple

FIELD WIRING

BK - black

BL - blue

UNLESS SPECIFIED

BR - brown

USE MINIMUM

60° Copper Wire

FACTORY WIRING

EF Failure Light

Off Delay Relay

SF Failure Light

Aux. Supply Contact

Fan Failure Light (Appl.)

SDR

Exhaust in Fire

Lights Out in Fire

DPDT Relay w/SF

DPDT Relay w/EF

Fire Relay (#1)

Extra Fire Relay (#3)

Extra Fire Relay (#2)

MUA Interface

Wire

PH FLA

Breaker

1

1

1

X

X

X

X

X

X

Shunt Trip Breaker

Air Flow Switch

Damper
Evap Cooler

PushButton

Gas Solenoid

Starter

Switch

Light

Ground

Fire Switch 

Exhaust Fan

Supply Fan
OverLoad

Contactor

Relay

Digitial Temperature Interlock

0 Mounted Sensors - Factory

3 Mounted Sensors - Field 

TC

TS

Temperature Controller

Temperature Sensor

TORQUE:

FIELD WIRING:

LABEL DESCRIPTION

WIRE COLOR

ALL WIRING 90°C 14 GA.

Controls

LISTED

43BM

COMMERCIAL APPLIANCE OUTLET CENTER

ELECTRICAL RATINGS: 120V, 1PHASE, 60HZ, 15A

FILE #E313951

LIGHT INPUT: 115VAC,

15AMPS FROM BREAKER

1400W max.

H2

S2

L1

LT

LT

N2

N

Switches Mounting - On Control Package

BK

B2

W2

WH

closed w/power at H1/N1 & fire system armed

open w/power at H1/N1 & fire system armed

(can be used for shunt trip, alarms, etc.)

Spare Relay Contacts

closed on fire or no power

open on fire or no power

22
24

A

B

B

A

NC3 BR

C3

NO3

RD

BK

NO4
NC4

A
B

R1

21

C4

32

BR

31

34

RD

BK

R1

(activated by FS1)

115/1 PHASE

2 WIRE

FROM BREAKER

L2

INPUT POWER

L1

N

OL1 

ST1

T1

L1 T1

T2

L2 T2

T3

L3 T3

G

Exh

FAN 1

208/3 PHASE

3 WIRE

FROM BREAKER

L3

L2

INPUT POWER

L1

OL2 

ST2

T1

L1 T1

T2

L2 T2

T3

L3 T3

G

Exh

FAN 2

230/1 PHASE

2 WIRE

FROM BREAKER

L2

INPUT POWER

L1

OL3 

ST3

T1

L1 T1

T2

L2 T2

T3

L3 T3

G

Supply

FAN 3

R

R

CONNECTIONS TO

TEMPERED MUA FAN

Switch Mounting - On Control Package

BL

OFF

S3

CONTROL INPUT: 115VAC, 15AMPS FROM BREAKER

H1

L1

N1

N

G

RD

S1

FACTORY MOUNTED SWITCH

FACTORY WIRING TO SWITCH

R LT1

S1N

WH

S1 OR

S1H

S1 OR

24

23

TC1

22

20

TC1

17

15

TC1

RD

11

12

R1

96

A1

OR

A2

ST1

WH

95

OL1

96

A1

OR

A2

ST2

WH

95

OL2

96

A1

YW

A2

ST3

WH

95

OL3

14

11

R1

YW

OR

D3

D1

D2

C

NO

BK(YW)

RD

RD(RD)

C1

NC

FS1

BR(BK)

NO1

NC1

BR

A1 R1 A2

WH

STH

STB1

STN

WH

BK

20.0

6.0

12.0

TEMPERATURE INTERLOCK CALIBRATION

1. PRESS SET BUTTON. 'St1' WILL APPEAR.

2. PRESS UP OR DOWN BUTTON TO NAVIGATE TO SET POINT THAT YOU WISH 

TO ADJUST ('St1', 'St2', OR 'St3').

3. PRESS SET BUTTON TO VIEW CURRENT SET POINT. PRESS UP OR DOWN 

BUTTON TO ADJUST AND PRESS SET BUTTON TO STORE VALUE.

4. PRESS SET + DOWN BUTTONS TOGETHER TO EXIT OR WAIT 1 MINUTE.

5. CHECK SYSTEM OPERATION BEFORE MAKING ADDITIONAL ADJUSTMENTS.

Spare Fire Switch Contact

(dry contacts for building alarm)

RD/RD

C2

NO2

NC2

BK/YW

BR/BK

C

NC
NO

Ansul / Amerex

RD/RD

BK/YW

BR/BK

FS2

NOTES:

DRAWING SHOWN DE-ENERGIZED AT L1 (TERM. #H1), 

W/ FIRE SYSTEM ARMED (NON-FIRE MODE). (NORMAL 

OPERATION, R1 & R2 ARE ENERGIZED) IF WALL 

MOUNTED PREWIRE, OR FIELD INSTALLED FIRE 

SYSTEM, THE FIRE SYSTEM MICROSWITCHES MUST 

BE FIELD WIRED.

F1-E

EF-1

1

115

1 16.0 12 ga 20 amp

F2-E

EF-2

0.5 208

3

2.4 14 ga 15 amp

F3-S

SF-1

0.75 230

1

6.9 14 ga 15 amp

COOL

BL

Y1

Y1

HEAT

W1

BL

W1

T1-B

T1-A

TS1

TC1

RD

2

1

3

11

12

4

WH

T2-A

T2-B

TS2

T3-A

T3-B

TS3

Содержание KFCC

Страница 1: ...FCC Field Connection Checklist 16 General Wiring Diagram 17 Testing 18 Operation 19 Troubleshooting 19 Maintenance 20 Frequently Asked Questions 20 Replacement Parts 21 Codes and Standards 21 Maintena...

Страница 2: ...with additional relays prewired to the fan starter s These additional relays are capable of turning on the kitchen exhaust and shutting down supply regardless of the present state of the fans via inte...

Страница 3: ...Octagon Extension Optional PN 830125 0 75 to 0 875 inch 19 0 to 22 2 mm diameter hole Hood Surface 1 2 3 1 PLACE THE J BOX PLATE INSIDE OF THE OCTAGON EXTENSIO RING AND PLACE OVER HOLE 2 DISASSEMBLE...

Страница 4: ...96 Temperature Sensor PN 384925 Octagon Cover PN 380926 2 inch typical 50 8 mm 19 525 inches 495 9 mm 3 inch air space 76 2 mm Additional Octagon Extension Optional PN 830125 0 75 to 0 875 inch 19 0 t...

Страница 5: ...tension PN 830125 Junction Box Plate PN 732396 19 525 inches 495 9 mm 3 inch air space 76 2 mm 2 inch typical 50 8 mm Exhaust Area Exploded View Components 2 inches 50 8 mm Hood Exhaust Collar front s...

Страница 6: ...t will need to be run to the panel as well to power the lights The KFCC can provide up to three light circuits Power for Hood Lights 115 VAC 15 amp circuit to terminals H2 and N2 first light circuit 1...

Страница 7: ...ections to Starters and Fans Fire System Integration Two Fire System Microswitches C NO BK YW NC FS1 BR BK C NO BK YW NC FS2 RD RD BR BK C1 NC1 NO1 G NOTE C2 NC2 and NO2 terminals are provided for a s...

Страница 8: ...WH S1 S1 S1H S1 S1H S1 Factory mounted switch Factory wiring to switch R LT1 S1N S1 S1H S1 S 1 B2 H2 R CONNECTIONS TO Remote Mounted Switch TEMPERED MUA FAN S1 LO S1 HI S1S S1F Two Fire System Micros...

Страница 9: ...Tempered Supply Heat Only To terminals R and W1 Tempered Supply Cool Only To terminals R and Y1 Tempered Supply Heat and Cool To terminals R common W1 heat and Y1 cool Connections from these terminals...

Страница 10: ...t wiring should be followed Please see either Switches Optional Lights on page 8 or Combination Light Fan Switch on page 9 for additional wiring information NOTE For lights out in fire option light ci...

Страница 11: ...T3 A T3 B TS3 LT SL3 SL4 115V STATUS LIGHT Status Lights Optional The option adds status lights to the face of the KFCC Power will have to be provided for each light in the field Status light s Bring...

Страница 12: ...al Temperature Interlock Thermostat Optional NONE EXHAUST AIR FLOW SWITCH FIELD WIRED T1 B T1 A TS1 TC1 2 1 3 11 12 4 T2 A T2 B TS2 T3 A T3 B TS3 LT SL3 SL4 115V STATUS LIGHT NOTE Do not connect tempe...

Страница 13: ...o store value 4 Press OUT1 OUT2 C F Set Set A U X OUT1 OUT2 C F Set Set A U X buttons together to exit set point menu or wait 1 minute Show Sensor Values Press OUT1 OUT2 C F Set Set A U X OUT1 OUT2 C...

Страница 14: ...ime Minutes 0 0 0 0 0 0 c23 Minimum Output 3 On Time Minutes 0 0 0 0 0 0 c31 On Time Fault Sensor 1 Cycle Minutes 1 0 1 0 1 0 c32 On Time Fault Sensor 2 Cycle Minutes 0 0 1 0 1 0 c33 On Time Fault Sen...

Страница 15: ...adjusted slightly depending of both ambient and cooking conditions The adjustment knob is located on the back of the thermostat Use a small blade screwdriver to make the adjustments 1 Turn countercloc...

Страница 16: ...y be directly wired to hood lights Thermal heat only terminals R W1 Thermal cool only terminals R Y1 Thermal heat and cool terminals R W1 Y1 MUA Interface if equipped To MUA Control Center terminals R...

Страница 17: ...WH closed w power at H1 N1 fire system armed open w power at H1 N1 fire system armed can be used for shunt trip alarms etc Spare Relay Contacts closed on fire or no power open on fire or no power 22 2...

Страница 18: ...cation of fan start up shut down cooking equipment The fan switch should still be in the off position Once cooking equipment has cooled the thermostat will open triggering the timer function in the ti...

Страница 19: ...with temperature interlock either thermostat style or digital style Check wiring to control panel With thermostat style interlock thermostats must be wired in parallel With digital style interlock sen...

Страница 20: ...ans to prevent fan on off cycling while the temperature in the exhaust duct can reach steady state Without the delay cycling could occur both on startup or shutdown of cooking equipment The delay is t...

Страница 21: ...perature Sensor RTD Dwyer TE IBN E0448 00 880601 Temperature Controller Programmed for 1 sensor Dwyer TSDIN 013 G 880602 Temperature Controller Programmed for 2 sensors Dwyer TSDIN 013 G 880603 Temper...

Страница 22: ...______________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ______________________...

Страница 23: ...______________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ______________________...

Страница 24: ...anties Greenheck s Kitchen Ventilation Systems Controls and Energy Management catalog provides additional information describing the equipment fan performance available accessories and specification d...

Отзывы: