14
Kitchen Fan Control Center
®
Factory Parameters
To access/adjust all factory parameters, follow these
instructions:
1 . Press and hold
OUT1
OUT2
°C
°F
Set
Set
A
U
X
button for 30 seconds or until ‘0’
appears .
NOTE
The controller is pre-programmed at the factory to
operate based on how many sensors were selected .
Adjustments (outside of the set point temperatures
discussed in calibration section) should only be made
under factory instruction . The list provided is for
reference only .
Temperature Controller Parameters
Description
Units
1 Sensor Program
2 Sensor Program
3 Sensor Program
St1
Setpoint Value Sensor 1
Degrees
90 .0
90 .0
90 .0
St2
Setpoint Value Sensor 2
Degrees
3 .0
90 .0
90 .0
St3
Setpoint Value Sensor 3
Degrees
3 .0
3 .0
90 .0
r01
Differential Sensor 1
Degrees
10 .0
10 .0
10 .0
r02
Differential Sensor 2
Degrees
1 .0
10 .0
10 .0
r03
Differential Sensor 3
Degrees
1 .0
1 .0
10 .0
r4
Minimum Setpoint Value
Degrees
-50 .0
-50 .0
-50 .0
r5
Maximum Setpoint Value
Degrees
150 .0
150 .0
150 .0
c01
Mode Sensor 1
Range
dir
dir
dir
c02
Mode Sensor 2
Range
inu
dir
dir
c03
Mode Sensor 3
Range
inu
inu
dir
c11
Minimum Output 1 Stop Time
Minutes
5 .0
5 .0
5 .0
c12
Minimum Output 2 Stop Time
Minutes
0 .0
5 .0
5 .0
c13
Minimum Output 3 Stop time
Minutes
0 .0
0 .0
5 .0
c21
Minimum Output 1 On Time
Minutes
0 .0
0 .0
0 .0
c22
Minimum Output 2 On Time
Minutes
0 .0
0 .0
0 .0
c23
Minimum Output 3 On Time
Minutes
0 .0
0 .0
0 .0
c31
On Time Fault Sensor 1 Cycle
Minutes
1 .0
1 .0
1 .0
c32
On Time Fault Sensor 2 Cycle
Minutes
0 .0
1 .0
1 .0
c33
On Time Fault Sensor 3 Cycle
Minutes
0 .0
0 .0
1 .0
c41
Off Time Fault Sensor 1 Cycle
Minutes
0 .0
0 .0
0 .0
c42
Off Time Fault Sensor 2 Cycle
Minutes
0 .0
0 .0
0 .0
c43
Off Time Fault Sensor 3 Cycle
Minutes
0 .0
0 .0
0 .0
P0
Temp Scale
Option
F
F
F
P11
Sensor 1 Calibration
Degrees
0 .0
0 .0
0 .0
P12
Sensor 2 Calibration
Degrees
0 .0
0 .0
0 .0
P13
Sensor 3 Calibration
Degrees
0 .0
0 .0
0 .0
P2
Decimal Point
Option
YES
YES
YES
P31
Sensor 1 Present
Option
YES
YES
YES
P32
Sensor 2 Present
Option
NO
YES
YES
P33
Sensor 3 Present
Option
NO
NO
YES
H2
Keypad Protection
Option
NO
NO
NO
H4
Serial Communications Address
Range
0
0
0
H5
Keypad Code
Range
0
0
0
H6
Type of Sensor
Option
Pt1
Pt1
Pt1
Shaded values are changed by the factory
2 . Press
OUT1
OUT2
°C
°F
Set
Set
A
U
X
button to enter parameter list .
3 . With
OUT1
OUT2
°C
°F
Set
Set
A
U
X
or
OUT1
OUT2
°C
°F
Set
Set
A
U
X
button navigate to the desired
parameter on the list of parameters .
4 . Press
OUT1
OUT2
°C
°F
Set
Set
A
U
X
button to see the current set value .
5 . Press either
OUT1
OUT2
°C
°F
Set
Set
A
U
X
or
OUT1
OUT2
°C
°F
Set
Set
A
U
X
button to set the desired new
value .
6 . Press
OUT1
OUT2
°C
°F
Set
Set
A
U
X
button to confirm it and exit to the
parameter list .
7 . Press
OUT1
OUT2
°C
°F
Set
Set
A
U
X
+
OUT1
OUT2
°C
°F
Set
Set
A
U
X
buttons together to exit the
programming menu or wait 1 minute (keypad
timeout) .