Kitchen Fan Control Center
®
Power to KFCC Cabinet and Lights
115 VAC power for controls (terminals H1, N1)
115 VAC power for hood lights, one per light circuit
(terminals H2, N2 | H3, N3 | H4, N4)
Connect lights, one per light circuit
(terminals B2, W2 | B3, W3 | B4, W4)
(Lights may be directly wired to switch)
Power for Fans
115/200/208/230/277 VAC power, single phase fans
from breaker (terminals L1, L2)
208/230/277/460/575 VAC power, three phase fans
from breaker (terminals L1, L2, L3)
115 VAC power for single phase to fan (contactor/
overload T3, terminal L2 is neutral)
208/230/277/460 VAC power to single phase fan
(contactor/overload T1, T3)
208/460/575 VAC power to three phase fan
(contactor/overload T1, T2, T3)
Fire System
Microswitch C, N .O ., and N .C . (terminals C1, NO1,
NC1)
Spare Fire Contacts
Spare, dry relay contact (terminals C3, NO3, NC3)
Spare, dry relay contact (terminals C4, NO4, NC4)
Switches
- if equipped
Fan, 1-Speed (terminals S_H, S_; S_N is neutral if
lighted)
Fan, 2-Speed (terminals S_F, S_S, S_)
Light (terminals H2, B2 or H3, B3 or H4, B4; may be
directly wired to hood lights)
Thermal, heat only (terminals R, W1)
Thermal, cool only (terminals R, Y1)
Thermal, heat and cool (terminals R, W1, Y1)
MUA Interface
- if equipped
To MUA Control Center (terminals R, G)
Power for Shunt Trip
- if equipped
Shunt trip breaker coil (terminals STH, STN)
Additional Fire Contacts
- if equipped
Spare, dry relay contact (terminals C9, NO9, NC9)
Spare, dry relay contact (terminals C10, NO10, NC10)
Additional Exhaust Contacts
- if equipped
Spare, dry relay contact (terminals C7, NO7, NC7)
Spare, dry relay contact (terminals C8, NO8, NC8)
Additional Supply Contacts
- if equipped
Spare, dry relay contact (terminals C5, NO5, NC5)
Spare, dry relay contact (terminals C6, NO6, NC6)
Exhaust Fan Failure Indicator
- if equipped
Field provided airflow switch or current sensor
(terminals AF1, AF2)
Supply Fan Failure Indicator
- if equipped
Field provided airflow switch or current sensor
(terminals AF3, AF4)
Status Lights (115 VAC)
- if equipped
Status light one (terminals SL1, SL2)
Status light two (terminals SL3, SL4)
Digital Style Temperature Interlock
- if equipped
Sensor(s) (terminals T_-A, T_-B)
Thermostat Style Temperature Interlock
- if equipped
Thermostat(s) (wired in parallel between terminals
T1-A, T1-B)
KFCC Field Connection Checklist