Kitchen Fan Control Center

®

Operation

1 . Turn fans on and off using the fan switch .
2 . 

If KFCC is configured to control hood lights,

 turn 

hood lights on and off using the light switch .

3 . 

If KFCC is configured with digital style 
temperature interlock,

 it is normal for the fan(s) to 

remain running after the switch is turned off . The 
exhaust temperature controller will shut down fans 
after heat is no longer present under the hood and the 
temperature is below the set point . In the event that 
the cooking equipment is started without turning the 
fans on manually, the fans will turn on automatically 
and remain running with the presence of heat under 
the hood . Once the temperature is below the set 
point, the fans will shut down .

4 . 

If KFCC is configured with thermostat style 
temperature interlock,

 it is normal for the fan(s) to 

remain running after the fan switch is turned off . The 
exhaust thermostat will open after heat is no longer 
present under the hood which will activate the timed 
relay to begin its countdown . Once time has expired, 
fans will shut down . The timed relay is adjustable 
from 1-100 minutes . The recommended time delay 
setting is approximately 20 minutes .

Troubleshooting

1.  Fan(s) do not turn on automatically upon cooking 
equipment activation

•  Confirm that the KFCC has been configured with 

temperature interlock, either thermostat style or 
digital style .

•  Check wiring to control panel . With thermostat style 

interlock, thermostats must be wired in parallel . With 
digital style interlock, sensors must be wired to the 
control panel separately .

•  Temperature set point is too high, decrease set point .
•  No power to fan(s), check breakers/starters/relays .

2.  Controller(s) in KFCC display EP1 or EP2 and EP3 
fan(s) will not shut off.

•  EP1, EP2 and EP3 represent sensor errors .
•  Disconnect the sensor from the system, and check 

resistance between the two wires on the sensor . At 
room temperature (77°F or 25°C), the sensor should 
read 1097 .4 ohms .

•  Check wiring connections between the sensor and 

control cabinet . 

3.  Fan(s) do not shut off.

•  Fan switch must be in the off position .
•  If the KFCC is configured with digital style 

temperature interlock, check the controller to 
determine if there is a sensor error of EP1, EP2 and/
or EP3 . If yes, refer to the controller display error 
message, item 2 above .

•  Cooking equipment is still hot, and the KFCC is 

configured with temperature interlock . Wait for the 
equipment to cool .

•  Temperature set point for temperature interlock is set 

too low, increase set point .

•  Check control circuit (fan starter) wiring .

4.  Exhaust fan(s) will not shut off, and supply fan(s) 
will not turn on.

•  Check hood for fire system dump .
•  If no fire system dump has occurred, check fire 

system wiring between fire system microswitch and 
control panel . 

5.  Fan(s) do not turn on quick enough.

•  Decrease temperature set point

Содержание KFCC

Страница 1: ...FCC Field Connection Checklist 16 General Wiring Diagram 17 Testing 18 Operation 19 Troubleshooting 19 Maintenance 20 Frequently Asked Questions 20 Replacement Parts 21 Codes and Standards 21 Maintena...

Страница 2: ...with additional relays prewired to the fan starter s These additional relays are capable of turning on the kitchen exhaust and shutting down supply regardless of the present state of the fans via inte...

Страница 3: ...Octagon Extension Optional PN 830125 0 75 to 0 875 inch 19 0 to 22 2 mm diameter hole Hood Surface 1 2 3 1 PLACE THE J BOX PLATE INSIDE OF THE OCTAGON EXTENSIO RING AND PLACE OVER HOLE 2 DISASSEMBLE...

Страница 4: ...96 Temperature Sensor PN 384925 Octagon Cover PN 380926 2 inch typical 50 8 mm 19 525 inches 495 9 mm 3 inch air space 76 2 mm Additional Octagon Extension Optional PN 830125 0 75 to 0 875 inch 19 0 t...

Страница 5: ...tension PN 830125 Junction Box Plate PN 732396 19 525 inches 495 9 mm 3 inch air space 76 2 mm 2 inch typical 50 8 mm Exhaust Area Exploded View Components 2 inches 50 8 mm Hood Exhaust Collar front s...

Страница 6: ...t will need to be run to the panel as well to power the lights The KFCC can provide up to three light circuits Power for Hood Lights 115 VAC 15 amp circuit to terminals H2 and N2 first light circuit 1...

Страница 7: ...ections to Starters and Fans Fire System Integration Two Fire System Microswitches C NO BK YW NC FS1 BR BK C NO BK YW NC FS2 RD RD BR BK C1 NC1 NO1 G NOTE C2 NC2 and NO2 terminals are provided for a s...

Страница 8: ...WH S1 S1 S1H S1 S1H S1 Factory mounted switch Factory wiring to switch R LT1 S1N S1 S1H S1 S 1 B2 H2 R CONNECTIONS TO Remote Mounted Switch TEMPERED MUA FAN S1 LO S1 HI S1S S1F Two Fire System Micros...

Страница 9: ...Tempered Supply Heat Only To terminals R and W1 Tempered Supply Cool Only To terminals R and Y1 Tempered Supply Heat and Cool To terminals R common W1 heat and Y1 cool Connections from these terminals...

Страница 10: ...t wiring should be followed Please see either Switches Optional Lights on page 8 or Combination Light Fan Switch on page 9 for additional wiring information NOTE For lights out in fire option light ci...

Страница 11: ...T3 A T3 B TS3 LT SL3 SL4 115V STATUS LIGHT Status Lights Optional The option adds status lights to the face of the KFCC Power will have to be provided for each light in the field Status light s Bring...

Страница 12: ...al Temperature Interlock Thermostat Optional NONE EXHAUST AIR FLOW SWITCH FIELD WIRED T1 B T1 A TS1 TC1 2 1 3 11 12 4 T2 A T2 B TS2 T3 A T3 B TS3 LT SL3 SL4 115V STATUS LIGHT NOTE Do not connect tempe...

Страница 13: ...o store value 4 Press OUT1 OUT2 C F Set Set A U X OUT1 OUT2 C F Set Set A U X buttons together to exit set point menu or wait 1 minute Show Sensor Values Press OUT1 OUT2 C F Set Set A U X OUT1 OUT2 C...

Страница 14: ...ime Minutes 0 0 0 0 0 0 c23 Minimum Output 3 On Time Minutes 0 0 0 0 0 0 c31 On Time Fault Sensor 1 Cycle Minutes 1 0 1 0 1 0 c32 On Time Fault Sensor 2 Cycle Minutes 0 0 1 0 1 0 c33 On Time Fault Sen...

Страница 15: ...adjusted slightly depending of both ambient and cooking conditions The adjustment knob is located on the back of the thermostat Use a small blade screwdriver to make the adjustments 1 Turn countercloc...

Страница 16: ...y be directly wired to hood lights Thermal heat only terminals R W1 Thermal cool only terminals R Y1 Thermal heat and cool terminals R W1 Y1 MUA Interface if equipped To MUA Control Center terminals R...

Страница 17: ...WH closed w power at H1 N1 fire system armed open w power at H1 N1 fire system armed can be used for shunt trip alarms etc Spare Relay Contacts closed on fire or no power open on fire or no power 22 2...

Страница 18: ...cation of fan start up shut down cooking equipment The fan switch should still be in the off position Once cooking equipment has cooled the thermostat will open triggering the timer function in the ti...

Страница 19: ...with temperature interlock either thermostat style or digital style Check wiring to control panel With thermostat style interlock thermostats must be wired in parallel With digital style interlock sen...

Страница 20: ...ans to prevent fan on off cycling while the temperature in the exhaust duct can reach steady state Without the delay cycling could occur both on startup or shutdown of cooking equipment The delay is t...

Страница 21: ...perature Sensor RTD Dwyer TE IBN E0448 00 880601 Temperature Controller Programmed for 1 sensor Dwyer TSDIN 013 G 880602 Temperature Controller Programmed for 2 sensors Dwyer TSDIN 013 G 880603 Temper...

Страница 22: ...______________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ______________________...

Страница 23: ...______________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ______________________...

Страница 24: ...anties Greenheck s Kitchen Ventilation Systems Controls and Energy Management catalog provides additional information describing the equipment fan performance available accessories and specification d...

Отзывы: