Kitchen Fan Control Center

®

®

Document 482413

Kitchen Fan Control Center

Installation, Operation and Maintenance Manual

Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, 
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure 
to comply with these instructions will result in voiding of the product warranty and may result in personal injury 
and/or property damage.

Table of Contents

General Description

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2

Receiving and Handling

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2

Installation

  Control Box   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3
  Switch Mounting   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3
  Temperature Sensor(s) - Hood Mounting   .  .  .  .  .  .  .  .  .  . 3-4
     

Duct Collar Mounting  .  .  .  .  .  .  .  . 4

  Thermostat - Hood Mounting   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 4
     

Duct Collar Mounting  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 5

Electrical Connections

  Power for KFCC    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 6
  Power for Hood Lights    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 6
  Power for Starters and Fans   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 7
  Fire System Integration   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 7
  Spare Fire Contacts  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
  Switches -   Fan, 1-Speed   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
     

Fan, 2-Speed   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8

    

Lights   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8

     

Tempered Supply, Heat Only  .  .  .  .  .  .  .  .  .  .  .  . 9

     

Tempered Supply, Cool Only  .  .  .  .  .  .  .  .  .  .  .  . 9

     

Tempered Supply, Heat and Cool   .  .  .  .  .  .  .  . 9

    Combination Fan/Light Switch  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 9
    Make-Up Air Interface    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 9
    Power for Shunt Trip  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 9
    Audible Alarm   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 9
    Lights Out in Fire    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 10
    Additional Fire Contacts  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 10
    Additional Exhaust Contacts   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 10
    Additional Supply Contacts   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11
    Exhaust Fan Failure Indicator  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11
    Supply Fan Failure Indicator    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11
    Status Lights  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11
    Temperature Interlock, Digital  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 12
    Temperature Interlock, Thermostat    .  .  .  .  .  .  .  .  .  .  .  .  .  . 12

Digital Temperature Interlock Configuration

   .  .  .  .  .  . 13-14

Thermostat Style Temperature  

Interlock Configuration

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 15

KFCC Field Connection Checklist

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 16

General Wiring Diagram

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 17

Testing

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 18

Operation

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19

Troubleshooting

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19

Maintenance

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 20

Frequently Asked Questions

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 20

Replacement Parts

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 21

Codes and Standards

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 21

Maintenance Log

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 22-23

Our Commitment

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 24

WARNING

Electrical shock hazard . Can cause equipment 
damage, personal injury or death . Service must only 
be performed by personal that are knowledgeable in 
the operation of the equipment being controlled .

CAUTION

Always disconnect power before working on or near 
the product . Lock and tag the disconnect switch or 
breaker to prevent accidental power up .

CAUTION

It is the responsibility of the installer to make sure both 
electrical and gas appliances shut down in the event 
of a fire or in the event of a power loss to the building 
when this sequence is required by the authority having 
jurisdiction .

General Safety Information

Only qualified personal should install this product .  
Personnel should have a clear understanding of these 
instructions and should be aware of general safety 
precautions . Improper installation can result in electric 
shock and other potential hazards .
1 .  Follow all local electrical and safety codes, as well as 

the National Electrical Code (NEC) and latest edition 
of the National Fire Protection Agency Standard for 
Ventilation Control and Fire Protection of Commercial 
Cooking Operations (NFPA 96) . Follow the Canadian 
Electrical Code (CEC) and ULC-S650 if installing this 
product in Canada .

2 .  Do not allow the electrical components of this 

product to come in contact with oil, grease, hot 
surfaces, water, or chemicals .

3 .  Verify the site can supply the necessary power for 

each fan and for the control panel .

Содержание KFCC

Страница 1: ...FCC Field Connection Checklist 16 General Wiring Diagram 17 Testing 18 Operation 19 Troubleshooting 19 Maintenance 20 Frequently Asked Questions 20 Replacement Parts 21 Codes and Standards 21 Maintena...

Страница 2: ...with additional relays prewired to the fan starter s These additional relays are capable of turning on the kitchen exhaust and shutting down supply regardless of the present state of the fans via inte...

Страница 3: ...Octagon Extension Optional PN 830125 0 75 to 0 875 inch 19 0 to 22 2 mm diameter hole Hood Surface 1 2 3 1 PLACE THE J BOX PLATE INSIDE OF THE OCTAGON EXTENSIO RING AND PLACE OVER HOLE 2 DISASSEMBLE...

Страница 4: ...96 Temperature Sensor PN 384925 Octagon Cover PN 380926 2 inch typical 50 8 mm 19 525 inches 495 9 mm 3 inch air space 76 2 mm Additional Octagon Extension Optional PN 830125 0 75 to 0 875 inch 19 0 t...

Страница 5: ...tension PN 830125 Junction Box Plate PN 732396 19 525 inches 495 9 mm 3 inch air space 76 2 mm 2 inch typical 50 8 mm Exhaust Area Exploded View Components 2 inches 50 8 mm Hood Exhaust Collar front s...

Страница 6: ...t will need to be run to the panel as well to power the lights The KFCC can provide up to three light circuits Power for Hood Lights 115 VAC 15 amp circuit to terminals H2 and N2 first light circuit 1...

Страница 7: ...ections to Starters and Fans Fire System Integration Two Fire System Microswitches C NO BK YW NC FS1 BR BK C NO BK YW NC FS2 RD RD BR BK C1 NC1 NO1 G NOTE C2 NC2 and NO2 terminals are provided for a s...

Страница 8: ...WH S1 S1 S1H S1 S1H S1 Factory mounted switch Factory wiring to switch R LT1 S1N S1 S1H S1 S 1 B2 H2 R CONNECTIONS TO Remote Mounted Switch TEMPERED MUA FAN S1 LO S1 HI S1S S1F Two Fire System Micros...

Страница 9: ...Tempered Supply Heat Only To terminals R and W1 Tempered Supply Cool Only To terminals R and Y1 Tempered Supply Heat and Cool To terminals R common W1 heat and Y1 cool Connections from these terminals...

Страница 10: ...t wiring should be followed Please see either Switches Optional Lights on page 8 or Combination Light Fan Switch on page 9 for additional wiring information NOTE For lights out in fire option light ci...

Страница 11: ...T3 A T3 B TS3 LT SL3 SL4 115V STATUS LIGHT Status Lights Optional The option adds status lights to the face of the KFCC Power will have to be provided for each light in the field Status light s Bring...

Страница 12: ...al Temperature Interlock Thermostat Optional NONE EXHAUST AIR FLOW SWITCH FIELD WIRED T1 B T1 A TS1 TC1 2 1 3 11 12 4 T2 A T2 B TS2 T3 A T3 B TS3 LT SL3 SL4 115V STATUS LIGHT NOTE Do not connect tempe...

Страница 13: ...o store value 4 Press OUT1 OUT2 C F Set Set A U X OUT1 OUT2 C F Set Set A U X buttons together to exit set point menu or wait 1 minute Show Sensor Values Press OUT1 OUT2 C F Set Set A U X OUT1 OUT2 C...

Страница 14: ...ime Minutes 0 0 0 0 0 0 c23 Minimum Output 3 On Time Minutes 0 0 0 0 0 0 c31 On Time Fault Sensor 1 Cycle Minutes 1 0 1 0 1 0 c32 On Time Fault Sensor 2 Cycle Minutes 0 0 1 0 1 0 c33 On Time Fault Sen...

Страница 15: ...adjusted slightly depending of both ambient and cooking conditions The adjustment knob is located on the back of the thermostat Use a small blade screwdriver to make the adjustments 1 Turn countercloc...

Страница 16: ...y be directly wired to hood lights Thermal heat only terminals R W1 Thermal cool only terminals R Y1 Thermal heat and cool terminals R W1 Y1 MUA Interface if equipped To MUA Control Center terminals R...

Страница 17: ...WH closed w power at H1 N1 fire system armed open w power at H1 N1 fire system armed can be used for shunt trip alarms etc Spare Relay Contacts closed on fire or no power open on fire or no power 22 2...

Страница 18: ...cation of fan start up shut down cooking equipment The fan switch should still be in the off position Once cooking equipment has cooled the thermostat will open triggering the timer function in the ti...

Страница 19: ...with temperature interlock either thermostat style or digital style Check wiring to control panel With thermostat style interlock thermostats must be wired in parallel With digital style interlock sen...

Страница 20: ...ans to prevent fan on off cycling while the temperature in the exhaust duct can reach steady state Without the delay cycling could occur both on startup or shutdown of cooking equipment The delay is t...

Страница 21: ...perature Sensor RTD Dwyer TE IBN E0448 00 880601 Temperature Controller Programmed for 1 sensor Dwyer TSDIN 013 G 880602 Temperature Controller Programmed for 2 sensors Dwyer TSDIN 013 G 880603 Temper...

Страница 22: ...______________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ______________________...

Страница 23: ...______________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ______________________...

Страница 24: ...anties Greenheck s Kitchen Ventilation Systems Controls and Energy Management catalog provides additional information describing the equipment fan performance available accessories and specification d...

Отзывы: