U-Match Series Cassette Type Unit
35
3.3.2 Electrical Parameters
Model
Power supply
Fuse
capacity
Circuit breaker
capacity
Min. sectional area
of power cord
V/Ph/Hz
A
A
mm
2
Indoor unit 220-240V ~50Hz
3.15
6
1.0
Model
Power supply
Circuit breaker
capacity
Min. sectional area of
power cord
V/Ph/Hz
A
mm
2
GU50W/A1-K
220-240V ~50Hz
16
1.5
GU71W/A1-K
220-240V ~50Hz
20
2.5
GU85W/A1-K
220-240V ~50Hz
25
2.5
GU100W/A1-M
380-415V 3N~50Hz
16
1.5
GU125W/A1-M
380-415V 3N~50Hz
16
1.5
GU140W/A1-M
380-415V 3N~50Hz
16
1.5
GU160W/A1-M
380-415V 3N~50Hz
16
1.5
NOTES:
①
.
Fuse is located on the main board.
②
.
Install a circuit breaker at every power terminal near the units (indoor and
outdoor units) with at least 3mm contact gap. The units must be able to be
plugged or unplugged.
③
.
Circuit breaker and power cord specifications listed in the above table are
determined based on the maximum power input of the units.
④
.
Specifications of power cords listed in the above table are applicable in a
working condition where ambient temperature is 40°C and multi-core
copper cable (e.g. YJV copper cable, with insulated PE and PVC sheath) is
protected by a conduit, and is resistant to 90°C in maximum (See IEC
60364-5-52). If working condition changes, please adjust the specifications
according to national standards.
⑤
.
Specifications of circuit breaker are based on a working condition where
the working temperature is 40°C. If working condition changes, please
adjust the specifications according to national standards.
⑥
.
Adopt 2pc of 0.75mm² power cords to be the communication cords
Содержание U-Match GU100T/A1-K
Страница 54: ......