88
HC
PFC (Power Factor Correction) Protection
Status:
During cooling & dehumidifying, indoor unit
operates while other functions stop; During
heating operation, complete unit stops
1.
Check for damage to the reactor and PFC
capacitor of the outdoor unit
2. Refer to troubleshooting procedure below
Error Code Diagnostics
HC Error Code
Start Troubleshooting
Correct according
to circuit diagram.
Yes
No
Yes
Is problem
corrected?
No
Check wiring of the reactor
(L) and PFC capacitor
(Outdoor Unit)
Are wires connected proper
with no short circuits?
Are wires connected proper
with no short circuits?
Remove the PFC Capacitor
and test resistance of the
two terminals.
Is the resistance
about zero?
Replace the
capacitor
Yes
Is problem
corrected?
Yes
No
No
Disconnect the reactor wires & measure
the resistance between the two terminals
of the reactor
Replace the reactor
Yes
Is problem
corrected?
Yes
No
Replace the AP1
control panel
End Troubleshooting
Is the reactor
damaged or
shorted?
Содержание TERRA09HP230V1A
Страница 13: ...13 Product Introduction Operation Characteristic Curve ...
Страница 14: ...14 Product Introduction Capacity Variation Ratio According to Temperature ...
Страница 16: ...16 Noise Criteria Curve Tables Product Introduction ...
Страница 54: ...54 Electrical Schematics ...
Страница 135: ...135 Gree Electric Appliances Inc C 2014 Cat No DFS TERRA HP 2SM Version 2 0 ...