Model
TERRA18HP230V1A
TERRA24HP230V1A
System Type
Heat Pump
Power Supply
208-230V / 60Hz
208-230V / 60Hz
Rated Current Cooling
Amps
7.4
8.5
Rated Current Heating
Amps
7.8
10.3
System Performance
Cooling Cap (Min/Max)
Btu/h
18,000 (4,600-22,180)
24,000 (6,826-29,352)
Heating Cap (Min/Max)
Btu/h
19,000 (3,400-24,900)
25,000 (7,509-37,543)
SEER/EER
21 / 12.0
21 / 12.0
HSPF/COP
9.8 / 3.5
9.2 / 3.3
Indoor Unit
Airflow
T/H/MH/M/ML/L/mute
CFM
588/512/465/418/371/330/282
706/647/589/530/471/412/353
Sound Pressure Level
T/H/MH/M/ML/L/mute
dBa
51/48/45/43/39/36/33
52/49/47/45/43/41/38
Unit Size (WxHxD)
Inches
40.1 x 12.6 x 9.1
46.4 x 12.8 x 10.4
Package Size (WxHxD)
Inches
43.2 x 15.6 x 13.4
49.2 x 16.2 x 14.0
Net/Gross Weight
Lbs
31 / 42
40 / 53
Outdoor Unit
Compressor Type
DC Inverter-Driven
Sound Pressure Level
dBa
56
56
Unit Size (WxHxD)
Inches
37.6 x 27.6 x 15.6
38.6 x 31.1 x 16.8
Package Size (WxHxD)
Inches
40.5 x 29.5 x 18.0
42.6 x 33.7 x 19.2
Net/Gross Weight
Lbs
110 / 121
153 / 164
Refrigerant/Charge
Oz.
R410A / 56.4
R410A / 77.6
Installation
Line Set Size (Liq-Suc)
Inches
1/4” - 5/8”
1/4” - 5/8”
Pre-Charge
Feet
25
25
Max Line Run
Feet
82
98
Max Elevation
Feet
33
33
MCA
Amps
15
20
MOCP
Amps
25
30
Wire Size to Outdoor Unit, #
of wires
AWG
10
10
Wire Size / # Wires
AWG
14 / 4
14 / 4
Physical & Electrical Data, cont.
Содержание TERRA09HP230V1A
Страница 13: ...13 Product Introduction Operation Characteristic Curve ...
Страница 14: ...14 Product Introduction Capacity Variation Ratio According to Temperature ...
Страница 16: ...16 Noise Criteria Curve Tables Product Introduction ...
Страница 54: ...54 Electrical Schematics ...
Страница 135: ...135 Gree Electric Appliances Inc C 2014 Cat No DFS TERRA HP 2SM Version 2 0 ...