DC Inverter U-match Series Floor Ceiling Type Unit
67
Notice
:
The use of silicon sealant may inhibit the
effectiveness of some types of leak detection equipment. Intrinsically
safe components do not have to be isolated prior to working on them.
5.4.3 Repair to Intrinsically Safe Components
Do not apply any permanent inductive or capacitance loads to the
circuit without ensuring that this will not exceed the permissible voltage
and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked
on while live in the presence of a flammable atmosphere. The test
apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer.
Other parts may result in the ignition of refrigerant in the atmosphere
from a leak.
5.4.4 Cabling
Check that cabling will not be subject to wear, corrosion, excessive
pressure, vibration, sharp edges or any other adverse environmental
effects. The check shall also take into account the effects of ageing or
continual vibration from sources such as compressors or fans.
5.4.5 Detection of Flammable Refrigerants
Under no circumstances shall potential sources of ignition be used
in the searching for or detection of refrigerant leaks. A halide torch (or
any other detector using a naked flame) shall not be used.
5.4.6 Removal and Evacuation
When breaking into the refrigerant circuit to make repairs
–
or for
any other purpose
–
conventional procedures shall be used. However, it
is important that best practice is followed since flammability is a