DC Inverter U-match Series Floor Ceiling Type Unit
25
Item
Model
Size of Fitting
Pipe(Inch)
Maximum
pipe
length
(m)
Biggest
drop
between
indoor and
outdoor
units (m)
Drain pipe
(outer
dimension ×
wall
thickness)
(mm)
Liquid
pipe
Gas
pipe
GUD35ZD/A-T
GUD35W/NhA-T
1/4
3/8
30
15
Ф
17×1.5
GUD50ZD/A-T
GUD50W/NhA-T
1/2
35
20
GUD71ZD/A-T
GUD71W/NhA-T
3/8
5/8
50
25
GUD85ZD/A-T
GUD85W/NhA-T
50
25
GUD100ZD/A-T
GUD100W/NhA-T
GUD100W/NhA-X
65
30
GUD125ZD/A-T
GUD125W/NhA-T
GUD125W/NhA-X
75
30
GUD140ZD/A-T
GUD140W/NhA-T
GUD140W/NhA-X
75
30
GUD160ZD/A-T
GUD160W/NhA-X
75
30
Connection pipe should adopt water-proof insulating material. Its
wall thickness should be 0.5-1.0mm and the pipe wall should be able to
withstand 6.0MPa. The longer the connection pipe is, the worse cooling
and heating performance it has.
When the drop between indoor and outdoor units is larger than
10m, an oil return bend should be added every 6 meters.