DC Inverter U-match Series Floor Ceiling Type Unit
40
and outdoor units and the communication cords. Make sure
the wires are not clamped too tight.
⑫
.
The wire gauge of power cord should be large enough.
Damaged power cord or other wires must be replaced by
specialized wires. Wiring work must be done according to
national wiring rules and regulations.
3.3.2 Electrical Parameters
3.3.2.1 Wire Specifications and Fuse Capacity
Model
Power supply
Fuse
capacity
Circuit
breaker
capacity
Min. sectional
area of power
cord
V/Ph/Hz
A
A
mm
2
Indoor
unit
220-240V ~50Hz
208-230V ~60Hz
3.15
6
1.0
Model
Power supply
Circuit
breaker
capacity
Min. sectional
area of power
cord
V/Ph/Hz
A
mm
2
GUD35W/NhA-T
220-240V ~50Hz
208-230V ~60Hz
16
1.5
GUD50W/NhA-T
16
1.5
GUD71W/NhA-T
20
2.5
GUD85W/NhA-T
25
2.5
GUD100W/NhA-T
32
4.0
GUD125W/NhA-T
32
4.0
GUD140W/NhA-T
40
6.0
GUD100W/NhA-X
380-415V 3N~50/60Hz
16
1.5
GUD125W/NhA-X
16
1.5
GUD140W/NhA-X
16
1.5
GUD160W/NhA-X
16
1.5
NOTICE:
①
.
Fuse is located on the main board.
②
.
Install a circuit breaker at every power terminal near the units
(indoor and outdoor units) with at least 3mm contact gap. The