DC Inverter U-match Series Floor Ceiling Type Unit
28
(2) Do not bend the pipes in an angle more than 90°.
(3) If the pipe is repeatedly bent or extended, it will become hard and
difficult to be bent or extended. So do not bend or extend the pipe
for more than 3 times.
(4)
When bending the pipe, do not
bend it excessively, otherwise it will
get broken. As shown beside, use
a sharp cutter to cut the heat
insulating pipe and bend it after the
pipe is exposed. After bending,
place the heat insulating pipe back
on the pipeline and fix it with
adhesive tape.
3.2.3.4 Connection Pipe of Indoor and Outdoor Units
NOTICE
①
.
Connect the pipe to the unit. Please follow the instructions stated in the figures
below. Use both spanner and torque wrench.
②
.
When connecting the tapered screw nut, first apply chilled machine oil on its
inner and outer surface and then screw it up for 3~4 circles.
③
.
Confirm the tightening torque by referring to the following table (If the screw
nut is over-twisted, it may be damaged and cause leakage).
④
.
Check whether gas leakage occurs to the connection pipe and then apply
thermal insulation, as shown below.
⑤
.
Wind sponge around the joint of gas pipe and heat insulation sheath of gas
collecting pipe.
⑥
.
Be sure to connect gas pipe after liquid pipe is connected.