GREE DC Inverter Side Discharge VRF
Ⅱ
for North America
74
Total capacity of downstream indoor units
C (Btu/h)
Pipe
(mm/inch)
Liquid pipe
(mm/inch)
C ≤19000
Φ12.7
(
Φ1/2)
Φ6.35
(
Φ1/4)
19000<
C≤48500
Φ15.9
(
Φ5/8)
Φ9.52
(
Φ3/8)
48500<
C≤76400
Φ19.05
(
Φ3/4)
Φ9.52
(
Φ3/8)
5.5 Dimension of Pipe between Indoor Branch and IDU
Dimension of pipe between indoor branch and IDU should be consistent with the dimension of
indoor pipe.
Fig. 9
Rated capacity of IDU
C(Btu/h)
Gas pipe
(mm/inch)
Liquid pipe
(mm/inch)
C
≤9600
Φ9.52
(
Φ3/8)
Φ6.35
(
Φ1/4)
9600<
C≤17000
Φ12.7
(
Φ1/2)
Φ6.35
(
Φ1/4)
17000<
C≤48000
Φ15.9
(
Φ5/8)
Φ9.52
(
Φ3/8)
48000<
C≤55000
Φ19.05
(
Φ3/4)
Φ9.52
(
Φ3/8)
55000<
C≤96000
Φ22.2
(
Φ7/8)
Φ9.52
(
Φ3/8)
NOTICE!
If the distance between IDU and its nearest branch is over 10m(33feet), then the liquid
pipe of IDU (rated capacity ≤17000Btu/h) shall be enlarged.
Содержание GMV-24WL/C-T
Страница 1: ...DC Inverter Side Discharge VRF for North America Capacity 24 kBtu h 60 kBtu h Rated Frequency 60 Hz...
Страница 4: ...GREE DC Inverter Side Discharge VRF for North America 1 PRODUCT...
Страница 12: ...GREE DC Inverter Side Discharge VRF for North America 9 CONTROL...
Страница 17: ...GREE DC Inverter Side Discharge VRF for North America 14...
Страница 18: ...GREE DC Inverter Side Discharge VRF for North America 15 Button Graphics...
Страница 65: ...GREE DC Inverter Side Discharge VRF for North America 62 Switchover of Software Languages...
Страница 66: ...GREE DC Inverter Side Discharge VRF for North America 63 INSTALLATION...
Страница 98: ...GREE DC Inverter Side Discharge VRF for North America 95 MAINTENANCE...
Страница 115: ...GREE DC Inverter Side Discharge VRF for North America 112 GMV 36WL A T U GMV 48WL A T U GMV 36WL C T U GMV 48WL C T U...
Страница 116: ...GREE DC Inverter Side Discharge VRF for North America 113 GMV 60WL A T U 4 Removal of Parts GMV 60WL C T U...
Страница 150: ...JF00302320...