GREE DC Inverter Side Discharge VRF
Ⅱ
for North America
66
(3) Test report: Certifications and quality test reports must be provided.
(4) The tensile strength must be at least 240 kgf/mm².
(5) Specifications requirement
R410A Refrigerant System
OD (mm/inch)
Wall Thickness (mm/inch)
Model
Φ6.35(1/4)
≥0.8(1/32)
0
Φ9.52(3/8)
≥0.8(1/32)
0
Φ12.70(1/2)
≥0.8(1/32)
0
Φ15.9(5/8)
≥1.0(1/25)
0
Φ19.05(3/4)
≥1.0(1/25)
0
(6) After the inner part of the copper pipe is cleaned and dried, the inlet and outlet must be sealed
tightly by using pipe caps, plugs or adhesive tapes. .
2.2 Condensate water pipe
(1) Pipes that can be used for air conditioner drainage include: water supplying UPVC pipe, PP-R
pipe, PP-C pipe, and HDG steel pipe;
(2) All relevant certificates and quality test reports are provided.
(3) Requirements for specifications and wall thickness
(4) Water supplying UPVC pipe:
Φ32mm×2mm
,
Φ40mm×2mm
,
Φ50mm×2.5mm;
(5) HDG steel pipe:
Φ25mm×3.25mm
,
Φ32mm×3.25mm
,
Φ40mm×3.5mm
,
Φ50mm×3.5mm.
2.3 Insulation material
(1) Rubber foam insulation material;
(2) Flame retardancy level: B1 or higher;
(3) Refractoriness: at least 120
℃
(248
℉
);
(4) The insulation thickness of condensate water pipe: at least 10 mm;
(5) When the diameter of copper pipe is equal to or greater than
Φ15.9 mm, the thickness of
insulation material should be at least 20 mm; when the diameter of copper pipe is less than
15.9 mm, the thickness of insulation material should be at least 15 mm.
2.4 Communication cable and control cable
Note:
For air conditioning units installed in places with strong electromagnetic interference, shielded
wire must be used as the communication cables of the IDU and wired controller, and shielded twisted
pairs must be used as the communication cables between IDUs and between the IDU and ODU.
Communication cable selection for ODU and IDUs
Содержание GMV-24WL/C-T
Страница 1: ...DC Inverter Side Discharge VRF for North America Capacity 24 kBtu h 60 kBtu h Rated Frequency 60 Hz...
Страница 4: ...GREE DC Inverter Side Discharge VRF for North America 1 PRODUCT...
Страница 12: ...GREE DC Inverter Side Discharge VRF for North America 9 CONTROL...
Страница 17: ...GREE DC Inverter Side Discharge VRF for North America 14...
Страница 18: ...GREE DC Inverter Side Discharge VRF for North America 15 Button Graphics...
Страница 65: ...GREE DC Inverter Side Discharge VRF for North America 62 Switchover of Software Languages...
Страница 66: ...GREE DC Inverter Side Discharge VRF for North America 63 INSTALLATION...
Страница 98: ...GREE DC Inverter Side Discharge VRF for North America 95 MAINTENANCE...
Страница 115: ...GREE DC Inverter Side Discharge VRF for North America 112 GMV 36WL A T U GMV 48WL A T U GMV 36WL C T U GMV 48WL C T U...
Страница 116: ...GREE DC Inverter Side Discharge VRF for North America 113 GMV 60WL A T U 4 Removal of Parts GMV 60WL C T U...
Страница 150: ...JF00302320...