GREE DC Inverter Side Discharge VRF
Ⅱ
for North America
109
(17) AC current protection for inverter compressor
Wired
controller
displays E0
LED3 dual-8
nixie tube
displays PP
Replace main
board
Work normally
(18) Communication malfunction between main contoller and driver of inverter compressor
Wired controlled
displays C2
LED3 dual-8 nixie
tube displays C2
Check whether the
main control CPU
board is inserted
well?
no
Work normally
Replace main
board
yes
Insert the CPU
board well
Содержание GMV-24WL/C-T
Страница 1: ...DC Inverter Side Discharge VRF for North America Capacity 24 kBtu h 60 kBtu h Rated Frequency 60 Hz...
Страница 4: ...GREE DC Inverter Side Discharge VRF for North America 1 PRODUCT...
Страница 12: ...GREE DC Inverter Side Discharge VRF for North America 9 CONTROL...
Страница 17: ...GREE DC Inverter Side Discharge VRF for North America 14...
Страница 18: ...GREE DC Inverter Side Discharge VRF for North America 15 Button Graphics...
Страница 65: ...GREE DC Inverter Side Discharge VRF for North America 62 Switchover of Software Languages...
Страница 66: ...GREE DC Inverter Side Discharge VRF for North America 63 INSTALLATION...
Страница 98: ...GREE DC Inverter Side Discharge VRF for North America 95 MAINTENANCE...
Страница 115: ...GREE DC Inverter Side Discharge VRF for North America 112 GMV 36WL A T U GMV 48WL A T U GMV 36WL C T U GMV 48WL C T U...
Страница 116: ...GREE DC Inverter Side Discharge VRF for North America 113 GMV 60WL A T U 4 Removal of Parts GMV 60WL C T U...
Страница 150: ...JF00302320...