GREE DC Inverter Side Discharge VRF
Ⅱ
for North America
134
Removal operation for plate heat exchanger
Remark: Before removing the plate he
at exchanger, please make sure that there’s no refrigerant inside the pipeline of
system and disconnect the power
Process
Photo
Operation Instruction
1. Twist off two
nuts fixing the
plate heat
exchanger with
wrench
Twist off two nuts
fixing the plate heat
exchanger with
wrench
2.Disconnect
inlet pipe and
outlet pipe of
plate heat
exchanger
Weld those 4
connection spots on
the plate heat
exchanger, and then
pull out the
connection pipe.
Note: During welding
process, do not let
flame burn out other
parts
3. Replace plate
heat exchanger
Replace plate heat
exchanger
Содержание GMV-24WL/C-T
Страница 1: ...DC Inverter Side Discharge VRF for North America Capacity 24 kBtu h 60 kBtu h Rated Frequency 60 Hz...
Страница 4: ...GREE DC Inverter Side Discharge VRF for North America 1 PRODUCT...
Страница 12: ...GREE DC Inverter Side Discharge VRF for North America 9 CONTROL...
Страница 17: ...GREE DC Inverter Side Discharge VRF for North America 14...
Страница 18: ...GREE DC Inverter Side Discharge VRF for North America 15 Button Graphics...
Страница 65: ...GREE DC Inverter Side Discharge VRF for North America 62 Switchover of Software Languages...
Страница 66: ...GREE DC Inverter Side Discharge VRF for North America 63 INSTALLATION...
Страница 98: ...GREE DC Inverter Side Discharge VRF for North America 95 MAINTENANCE...
Страница 115: ...GREE DC Inverter Side Discharge VRF for North America 112 GMV 36WL A T U GMV 48WL A T U GMV 36WL C T U GMV 48WL C T U...
Страница 116: ...GREE DC Inverter Side Discharge VRF for North America 113 GMV 60WL A T U 4 Removal of Parts GMV 60WL C T U...
Страница 150: ...JF00302320...